Safe Torque Off
6-1
AC30 series Variable Speed Inverter
Chapter 6
Safe Torque Off SIL3/PLe
General Information
THIS EQUIPMENT IF USED INCORRECTLY IS POTENTIALLY DANGEROUS. THEREFORE UNDER NO CIRCUMSTANCES
SHOULD IT BE USED BEFORE THESE INSTRUCTIONS HAVE BEEN READ AND UNDERSTOOD BY THE END USER WHO
SHOULD BE APPROPRIATELY QUALIFIED TO OPERATE THE EQUIPMENT.
This section provides general information about Safe Torque Off (STO).
Two safety functions can be implemented with the inverter: STO and Safe Stop 1 (SS1). In order to meet all aspects of STO and SS1, an external safety
control unit should be used.
To implement Safe Stop 1 (SS1), the external safety control unit causes the drive to decelerate to rest. Once at rest, it invokes STO in the inverter.
Please refer to EN61800-5-2:2007 para 4.2.2.3 for the formal definitions.
It is the user’s responsibility to:
1) Risk assess the machine.
2) Design, implement and assess an appropriate solution for each application to meet all relevant safety requirements.
Note: STO is an electronic inhibit intended for use during normal operation of the machine. It is not intended for use during machine maintenance,
repair, replacement or other similar activities. For these activities recognised electrical power isolation devices and lock-off procedures should be used.
The inverter STO function is a factory-fitted and factory-tested feature. See the section “Safety Warnings and Limitations” on page 6-18.
Summary of Contents for LINKnet AC30P
Page 47: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 49: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 51: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 53: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 55: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 153: ...Setup Wizard 9 28 AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 161: ...10 8 Trips Fault Finding AC30 series Variable Speed Inverter...