Safety
1-3
AC30 series Variable Speed Inverter
WARNING! - Ignoring the following may result in injury or damage to equipment
SAFETY
Where there is conflict between EMC and Safety requirements, personnel safety shall always take precedence.
Never perform high voltage resistance checks on the
wiring without first disconnecting the inverter from the
circuit being tested.
Whilst ensuring ventilation is sufficient, provide guarding
and /or additional safety systems to prevent injury or
damage to equipment.
When replacing an inverter in an application and before
returning to use, it is essential that all user defined
parameters for the product’s operation are correctly
installed.
All control and signal terminals are SELV, i.e. protected by double
insulation. Ensure all external wiring is rated for the highest system
voltage.
Thermal sensors contained within the motor must have at least
basic insulation.
All exposed metalwork in the Inverter is protected by basic
insulation and bonded to a safety earth.
RCDs are not recommended for use with this product but, where
their use is mandatory, only Type B RCDs should be used.
EMC
In a domestic environment this product may cause radio
interference in which case supplementary mitigation
measures may be required.
This equipment contains electrostatic discharge (ESD)
sensitive parts. Observe static control precautions when
handling, installing and servicing this product.
This is a product of the restricted sales distribution class according
to IEC 61800-3. It is designated as “professional equipment” as
defined in EN61000-3-2. Permission of the supply authority shall be
obtained before connection to the low voltage supply.
WARNING! – Control Unit Removal / Fitting
Isolate supply before plugging or unplugging control unit to the power stack.
Summary of Contents for LINKnet AC30P
Page 47: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 49: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 51: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 53: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 55: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 153: ...Setup Wizard 9 28 AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 161: ...10 8 Trips Fault Finding AC30 series Variable Speed Inverter...