Setup Wizard
9-6
AC30 series Variable Speed Inverter
PNO
Parameter
Validity
Comment
IM
VHz
IM
VECT
PMAC AFE
0478 PMAC SVC Start Cur
●
The current level during the startup procedure.
0479 PMAC SVC Start Speed
●
The speed setpoint at which the speed control is switched from an
open loop mode to a closed loop mode during the startup procedure
0464 100% Speed in RPM
●
●
●
This is the speed in rpm at which the motor will turn when given a
speed demand of 100%.
0486 Acceleration Time
●
●
●
The time that the inverter will take to ramp the setpoint from 0.00% to
100.00% when Ramp Type is LINEAR.
0487 Deceleration Time
●
●
●
The time that the inverter will take to ramp the setpoint from 100.00%
to 0.00% when Ramp Type is LINEAR.
1257 Seq Stop Method VHz
●
Selects stopping mode that the controller will use once the run
command has been removed when in Volts/Hertz control mode,
0484 Seq Stop Method SVC
●
Selects stopping mode that the controller will use once the run
command has been removed when in Sensorless Vector or Closed
Loop Vector control mode.
0422 VHz Shape
●
Selects the Volts to Frequency curve.
0390 Duty Selection
●
●
●
Selects the inverter rating. Affects the ratio of nominal current
compared with maximum overload current.
1730 AFE Inductance
● Total inductance (3% + 5%) in the AFE configuration.
1711 AFE VDC Demand
● DC Link level demand in voltage control mode.
1693 AFE Current Control
● Sets AFE in current control mode.
1705 AFE Iq Demand
● Reactive power current demand.
1704 AFE Id Demand
● Active power current demand.
Fieldbus Options
This section is only shown if a communications option is fitted.
PNO
Parameter
Comment
0044
Comms Required
This defaults to match the communications option that is fitted. If no option is required select NONE. Selecting
a different option will result in a configuration error.
These parameters are shown when the CANopen option is fitted.
PNO
Parameter
Comment
0044 Comms Required
CANOPEN
Refer to CANopen Technical Manual HA501841U001
0212 CANopen Node Address
●
0213 CANopen Baud Rate
●
0048 Comms Trip Enable
●
Summary of Contents for LINKnet AC30P
Page 47: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 49: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 51: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 53: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 55: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 153: ...Setup Wizard 9 28 AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 161: ...10 8 Trips Fault Finding AC30 series Variable Speed Inverter...