Safe Torque Off
Hybrid Actuation System Cylinders
SSeerriieess HHAASS 550000
Catalog HY08-
SSaaffee TToorrqquuee OOffff
W
WAARRNNIINNGG:: This product can expose you to chemicals including LLeeaadd aanndd LLeeaadd CCoom
mppoouunnddss
which are known to the State of
PPRROOPP 6655 W
WAARRNNIINNGG
California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
PPaarrkkeerr HHaannnniiffiinn CCoorrppoorraattiioonn
Cylinder Division
Des Plaines, Illinois
70
wwwwww..ppaarrkkeerr..ccoom
m/cylinder
•
SSTTOO tteesstt
RReegguullaarr CChheecckk,, AAccttiivviittyy
EExxppeecctteedd rreeaaccttiioonn aanndd eeffffeecctt
1
Ensure that no harm can come to personnel or equipment if
the motor turns.
2
Apply +24V DC to terminals X11/01 and X11/03.
No error must be present in the drive system
3
Apply power to the drive.
X11/05 and /06 must be OFF.
No error must be present in the drive system.
4
Try to start the drive with a non-zero setpoint. This setpoint
value will be referred to as SPT1 for brevity in these tests.
Leave this set throughout all tests.
The drive should start and the motor should turn at
SPT1.
X11/05 and /06 must remain OFF.
5
Remove connections to X11/01 and X11/03 within 1 second of
each other.
Drive must stop immediately, and report STO trip.
X11/05 and /06 must be ON.
6
Re-apply 24V to X11/01 and X11/03.
STO trip indication must remain.
X11/05 and /06 must turn OFF.
7
Try to restart drive.
STO trip indication should clear.
Drive must restart at SPT1.
8
Stop the drive.
Test is complete.
Drive must stop.
RReegguullaarr CChheecckk
A comprehensive check must take precedence if it coincides with a regular check.
A regular check is intended only to demonstrate the STO is functional. It will not always detect the loss of a single
channel. It is therefore important for the user and / or machinery builder to determine the frequency of the
comprehensive checks based on their knowledge and application of the machine.
TThhee ffoolllloowwiinngg tteessttss sshhoouulldd bbee ppeerrffoorrm
meedd::
Symptom
Examine:
Probable cause
Remedy
6901 MMI display
User
output
4
User inputs
5
Drive won’t start
when given a
start command
*** TRIPPED *** SAFE
TORQUE OFF
On
Both < 15V
STO is invoked.
When safe to do so, connect X11/01
and X11/03 to 24V ± 10%
*** TRIPPED *** SAFE
TORQUE OFF
Off
Both >15V and
< 30V
Fault latch might
have tripped
Remove all power from drive and re-
apply. If symptom persists, immediately
return the 890 for repair. See the
DANGER box below.
Any other trip
message, e.g.
overvoltage
Off
Both >15V and
< 30V
Drive is tripped,
but not due to
STO.
Reset the trip, and remove its cause.
If symptom persists, return the 890
for repair.
Any other message
Off
Both >15V and
< 30V
Faulty hardware
Return for repair
Drives starts
unexpectedly
Don’t care
Don’t care
Both < 5V
Faulty hardware
Immediately return the 890 for repair.
See the DANGER box below.
Don’t care
Off
Both > 5V
STO not invoked
by the user.
Use STO according to instructions
elsewhere in this chapter.
Drive fails
comprehensive
or regular STO
test
Don’t care
Don’t care
Don’t care
Faulty hardware
Immediately return the 890 for repair.
See the DANGER box below.
TTrroouubblleesshhoooottiinngg
The above table is only a guide. It may not be a comprehensive list of all possible symptoms relating to STO. Parker Hannifin
Manufacturing will not accept responsibility for any consequences arising from its incompleteness or inaccuracy.
4
Continuity through X11/05 and X11/06
5
Measure X11/01 and X11/03 relative to X11/02 or X11/04
Regular Check
Troubleshooting