2: Calibrating the Control Board 

NO POWER IS CONNECTED AT THIS STAGE 

2.1

 

Lift the hinged terminal cover to reveal 
the control board. 
Enter the settings for Armature 
Current, Field Current and Armature 
Voltage. 

 

X100

X10

X1

X10

X1

X0.1

SW1            SW2             SW3             SW4             SW5            SW6

IA CAL

IF CAL

ON

1
2
3
4

VA CAL

SW7

 

Armature 
Current 
(IA CAL) 

Note the maximum armature current from the motor rating plate and set this value using SW1, SW2 and SW3. 
The switches set Amps in hundreds, tens and units. The illustration shows an IA CAL setting of 77A. 

Field 
Current 
(IF CAL) 

Note the nominal field current from the motor rating plate and set this value using SW4, SW5 and SW6. The 
switches set Amps in tens, units and tenths. The illustration shows an IF CAL setting of 5.7A. The maximum 
current is 19.9A, setting a higher value than this results in 0A. 

Armature 
Voltage 
(VA CAL) 
 

Set this using the 4-way 
switch, SW7. The switch 
sets voltage according to 
the table. The illustration 
shows a VA CAL setting of 
200V.

 (A “1” indicates that 

the switch is ON).

 

 

VA 

Armature Volts VA (Volts) 

Switch 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 

1  1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 
2  1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 
3  1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 
4  1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 

 

2.2

 

CONNECT THE AUXILIARY SUPPLY:

 Remove 3-phase fuses (

6

). Re-instate branch circuit protection or circuit 

breaker (

8

). Check that the auxiliary voltage is correct. The MMI will now display the Welcome screen. 

AUXILIARY POWER ONLY IS CONNECTED AT THIS STAGE 

Use a digital voltmeter to check for +24V rail at terminal C9, +10V rail at terminal B3, -10V rail  
at terminal B4. The drive will be using the default speed feedback option ARM VOLTS FBK.  

 
 

MMI Menu Map 

 

 

 

SETUP PARAMETERS 

 

 

 

 

 

 

 

 

 

 

 

SPEED LOOP 

 

 

 

 

 

 

 

 

 

SPEED FBK SELECT 

Summary of Contents for DC590C Series

Page 1: ...that You have read and understood the Safety Information provided separately I S S U E 1 Q Qu ui ic ck kS St ta ar rt t WARRANTY Parker SSD Drives warrants the goods against defects in design material...

Page 2: ...air clearances to be maintained above and below drives and other equipment additive when two units are mounted together Overall Dimensions Fixing Centres Frame Current Rating A Weight Kg lbs Width Hei...

Page 3: ...em of more than one drive connect all clean earth rails together and only connect to the dirty earth rail 2 at one point Motor Earth Ground Connect an earth ground wire to the motor from the dirty ear...

Page 4: ...t Breaker 9 3 Power Supply Cable 10 Terminal Rail 11 Dirty Earth Ground Rail A 1 Pole MCB B Control Transformer C 2 Pole MCB D Fan Fuses E Motor Overload Protection F Emergency Stop Relay G Double Ins...

Page 5: ...ust be closed for the drive to run Speed Demand Uni directional A1 A4 B3 The 10K potentiometer adjusts the speed setpoint Zero speed Terminal A1 0V input Maximum forward speed 100 Terminal B3 10V inpu...

Page 6: ...the Drive Motor Field D3 F D4 F Connect shield between motor and earth rail These terminals provide an internal motor field supply fused by 10A fuses If the motor has no field connections is a permane...

Page 7: ...8 Disconnect the load from the motor shaft if possible If there is any doubt about the integrity of a particular installation insert a high wattage resistor i e fire elements in series with the motor...

Page 8: ...tting a higher value than this results in 0A Armature Voltage VA CAL Set this using the 4 way switch SW7 The switch sets voltage according to the table The illustration shows a VA CAL setting of 200V...

Page 9: ...the Start Run command from C3 The main 3 phase contactor should open and remain de energised IMPORTANT The main contactor should never be operated by any means other than the drive s internal controls...

Page 10: ...Terminal A1 0V input Check that 3 phase mains is applied to the power terminals L1 L2 and L3 Check the correct field voltage appears between the field output terminals D3 and D4 This is high voltage...

Page 11: ...4 Autotuning This process tunes the drive to the connected motor Initial conditions must be Main contactor open i e terminal C3 0V Program Stop terminal B8 Coast Stop terminal B9 and Enable terminal...

Page 12: ...ions below to make the installation application specific CHAPTER 3 Connection Diagrams Control Connections Optional Equipment CHAPTER 4 Selecting Speed Feedback Initial Start up Routine the full routi...

Page 13: ...RM VOLTS FBK 1 ANALOG TACH 2 ENCODER 3 ENCODER ANALOG for Parker SSD Drives use Refer to SPEED LOOP ENCODER LINES 24 10 to 5000 The number of lines must be set to match the type of encoder being used...

Page 14: ...available is 200 for 10 seconds 150 for 30 seconds Power Supply Details 3 Phase Supply 3 phase 50 60Hz earth referenced TN and non earth referenced IT Operating Suppy Tolerance 10 Voltage Ranges 220 t...

Reviews: