Electrical Installation 

NOTE 

 

Refer to the Safety and EMC sheets provided with the drive. 

An EMC compliant installation is shown.  

Earth/Ground Connections 

IMPORTANT

 

Refer to "Permanent Earthing" on the Installation Diagram. 

Earth/Ground Rails 

 

Provide a (dirty) earth/ground rail (

11

) inside the cubicle. Connect it to an external earth/ground, 

PE.

 

 
Provide a (clean) earth/ground rail (

2

) inside the cubicle, connected directly to the (dirty) earth/ground rail and insulated 

from the mounting panel. This is used for all signal and control cabling. 
Note:  In a system of more than one drive connect all (clean) earth rails together and only connect to the (dirty) earth rail 
(

2

) at one point. 

Motor Earth/Ground 

 

Connect an earth/ground wire to the motor from the (dirty) earth/ground rail. Connect shield between the motor and (dirty) 
earth/ground rail. 

Drive Earth/Ground

 

 

Connect an earth/ground wire from the (dirty) earth/ground rail to the drive's power terminal(s) marked PE 

35 - 270A units 

 

M6, 6.8Nm (5.0lb.ft) 

Environmental Conditions 

Operating ambient temperature  Frame 1 (35A to 70A) 

 

0ºC to 45ºC (32ºF to 113ºF)  

     Frame 

(110A 

to 

270A) 

0ºC to 35ºC (32ºF to 95ºF)  

Enclosure rating 

 

 

IP00 (Europe), UL(cUL) Open Type (North America/Canada)  

Atmosphere 

Dust free, non flammable, non corrosive, <85% humidity, Pollution Degree 2, 
non-condensing 

Summary of Contents for DC590C Series

Page 1: ...that You have read and understood the Safety Information provided separately I S S U E 1 Q Qu ui ic ck kS St ta ar rt t WARRANTY Parker SSD Drives warrants the goods against defects in design material...

Page 2: ...air clearances to be maintained above and below drives and other equipment additive when two units are mounted together Overall Dimensions Fixing Centres Frame Current Rating A Weight Kg lbs Width Hei...

Page 3: ...em of more than one drive connect all clean earth rails together and only connect to the dirty earth rail 2 at one point Motor Earth Ground Connect an earth ground wire to the motor from the dirty ear...

Page 4: ...t Breaker 9 3 Power Supply Cable 10 Terminal Rail 11 Dirty Earth Ground Rail A 1 Pole MCB B Control Transformer C 2 Pole MCB D Fan Fuses E Motor Overload Protection F Emergency Stop Relay G Double Ins...

Page 5: ...ust be closed for the drive to run Speed Demand Uni directional A1 A4 B3 The 10K potentiometer adjusts the speed setpoint Zero speed Terminal A1 0V input Maximum forward speed 100 Terminal B3 10V inpu...

Page 6: ...the Drive Motor Field D3 F D4 F Connect shield between motor and earth rail These terminals provide an internal motor field supply fused by 10A fuses If the motor has no field connections is a permane...

Page 7: ...8 Disconnect the load from the motor shaft if possible If there is any doubt about the integrity of a particular installation insert a high wattage resistor i e fire elements in series with the motor...

Page 8: ...tting a higher value than this results in 0A Armature Voltage VA CAL Set this using the 4 way switch SW7 The switch sets voltage according to the table The illustration shows a VA CAL setting of 200V...

Page 9: ...the Start Run command from C3 The main 3 phase contactor should open and remain de energised IMPORTANT The main contactor should never be operated by any means other than the drive s internal controls...

Page 10: ...Terminal A1 0V input Check that 3 phase mains is applied to the power terminals L1 L2 and L3 Check the correct field voltage appears between the field output terminals D3 and D4 This is high voltage...

Page 11: ...4 Autotuning This process tunes the drive to the connected motor Initial conditions must be Main contactor open i e terminal C3 0V Program Stop terminal B8 Coast Stop terminal B9 and Enable terminal...

Page 12: ...ions below to make the installation application specific CHAPTER 3 Connection Diagrams Control Connections Optional Equipment CHAPTER 4 Selecting Speed Feedback Initial Start up Routine the full routi...

Page 13: ...RM VOLTS FBK 1 ANALOG TACH 2 ENCODER 3 ENCODER ANALOG for Parker SSD Drives use Refer to SPEED LOOP ENCODER LINES 24 10 to 5000 The number of lines must be set to match the type of encoder being used...

Page 14: ...available is 200 for 10 seconds 150 for 30 seconds Power Supply Details 3 Phase Supply 3 phase 50 60Hz earth referenced TN and non earth referenced IT Operating Suppy Tolerance 10 Voltage Ranges 220 t...

Reviews: