background image

CONFIGURE DRIVE Menu 

CONFIGURE DRIVE (MMI view) 

 

Parameter Tag 

Range 

SETUP 

PARAMETERS 

 

 

Function Blocks 

 

 

FLD. CTRL MODE 

209 

See below 

 

Selects between open-loop VOLTAGE CONTROL or closed-loop 
CURRENT CONTROL. 

 

 

Refer to 

FIELD CONTROL

 

 
 

 
 

FLD. VOLTS RATIO 

210 

0.0 to 100.0 % (h) 

 

Sets the output dc field voltage as a ratio of the RMS FIELD supply voltage 
when FLD CTRL MODE is set to VOLTAGE CONTROL. 

 

Refer to 

FIELD CONTROL

 

 
 

 
 

MAIN CURR. LIMIT 

421 

0.00 to 200.00 % 

 

Independent symmetric current clamp.  Sets symmetric clamps outside scaling  
from the CUR. LIMIT/SCALER parameter. 

 

Refer to 

CURRENT LOOP

 

 
 

 
 

AUTOTUNE 18 

OFF/ARMATURE 

 

Turns the AUTOTUNE procedure on.  Refer to Chapter 4:  “Operating the Drive”- 
Performance Adjustment. 

 

 

Refer to 

AUTOTUNE

 

 
 

 
 

SPEED FBK SELECT 

47 

See below 

 

Determines the source of the speed feedback signal.  The default, ARM VOLTS FBK,  
uses internal circuitry to derive the speed feedback.  The other selections require the 
appropriate external device to provide the feedback signal. 
0 : ARM VOLTS FBK 
1 : ANALOG TACH 
2 : ENCODER 
3 : ENCODER/ANALOG – for Parker SSD Drives use 

 

Refer to 

SPEED LOOP

 

 
 

 

 

ENCODER LINES 

24 

10 to 5000 

 

The number of lines must be set to match the type of encoder being used.   
Incorrect setting of this parameter will result in an erroneous speed measurement. 
The 5901 microtach has 1000 lines per revolution as standard.  Proprietary encoders 
of other specifications can be normalised by setting this parameter as appropriate. 

Refer to 

ENCODER

 

 
 

 
 

ENCODER RPM 

22 

0 to 6000 

 

Motor top speed setting (100%) when using encoder feedback. 

 

Refer to 

ENCODER

 

 
 

 
 

ENCODER SIGN 

49 

 NEGATIVE / POSITIVE 

 

Since the encoder feedback cannot be reversed electrically, the signal polarity can 
be reversed by the control software. 

 

It is necessary to set up this parameter when in encoder feedback closed-loop speed 
control mode, as the encoder direction must be correct for this mode to operate.

 

Refer to 

ENCODER

 

 
 

 
 

SPD.INT.TIME 

13 

0.001 to 30.000 s 

 

Speed loop PI integral gain adjustment.

   

 

Refer to 

SPEED LOOP

 

 
 

 

 

SPD.PROP.GAIN 

14 

0.00 to 200.00 

 

Speed loop PI proportional gain adjustment. 

Refer to 

SPEED LOOP

 

 
 
 
 

For more information refer to 
the above function blocks in 
the Product Manual 

Summary of Contents for DC590C Series

Page 1: ...that You have read and understood the Safety Information provided separately I S S U E 1 Q Qu ui ic ck kS St ta ar rt t WARRANTY Parker SSD Drives warrants the goods against defects in design material...

Page 2: ...air clearances to be maintained above and below drives and other equipment additive when two units are mounted together Overall Dimensions Fixing Centres Frame Current Rating A Weight Kg lbs Width Hei...

Page 3: ...em of more than one drive connect all clean earth rails together and only connect to the dirty earth rail 2 at one point Motor Earth Ground Connect an earth ground wire to the motor from the dirty ear...

Page 4: ...t Breaker 9 3 Power Supply Cable 10 Terminal Rail 11 Dirty Earth Ground Rail A 1 Pole MCB B Control Transformer C 2 Pole MCB D Fan Fuses E Motor Overload Protection F Emergency Stop Relay G Double Ins...

Page 5: ...ust be closed for the drive to run Speed Demand Uni directional A1 A4 B3 The 10K potentiometer adjusts the speed setpoint Zero speed Terminal A1 0V input Maximum forward speed 100 Terminal B3 10V inpu...

Page 6: ...the Drive Motor Field D3 F D4 F Connect shield between motor and earth rail These terminals provide an internal motor field supply fused by 10A fuses If the motor has no field connections is a permane...

Page 7: ...8 Disconnect the load from the motor shaft if possible If there is any doubt about the integrity of a particular installation insert a high wattage resistor i e fire elements in series with the motor...

Page 8: ...tting a higher value than this results in 0A Armature Voltage VA CAL Set this using the 4 way switch SW7 The switch sets voltage according to the table The illustration shows a VA CAL setting of 200V...

Page 9: ...the Start Run command from C3 The main 3 phase contactor should open and remain de energised IMPORTANT The main contactor should never be operated by any means other than the drive s internal controls...

Page 10: ...Terminal A1 0V input Check that 3 phase mains is applied to the power terminals L1 L2 and L3 Check the correct field voltage appears between the field output terminals D3 and D4 This is high voltage...

Page 11: ...4 Autotuning This process tunes the drive to the connected motor Initial conditions must be Main contactor open i e terminal C3 0V Program Stop terminal B8 Coast Stop terminal B9 and Enable terminal...

Page 12: ...ions below to make the installation application specific CHAPTER 3 Connection Diagrams Control Connections Optional Equipment CHAPTER 4 Selecting Speed Feedback Initial Start up Routine the full routi...

Page 13: ...RM VOLTS FBK 1 ANALOG TACH 2 ENCODER 3 ENCODER ANALOG for Parker SSD Drives use Refer to SPEED LOOP ENCODER LINES 24 10 to 5000 The number of lines must be set to match the type of encoder being used...

Page 14: ...available is 200 for 10 seconds 150 for 30 seconds Power Supply Details 3 Phase Supply 3 phase 50 60Hz earth referenced TN and non earth referenced IT Operating Suppy Tolerance 10 Voltage Ranges 220 t...

Reviews: