Dewpoint Switch Cofigurations
ECO Set Point
At the end of each 2 ½ minute regeneration cycle, the exhaust valve will close and the purge air will repressurise the off-line column, ready for
use. At this point, the dryer controller will check the dewpoint sensor. If the compressed air is drier than the dewpoint for which the dryer was
selected (the ECO Set Point), this indicates that there is drying capacity remaining in the on-line desiccant bed. The EST- Energy Saving
Technology will then override the fixed cycle, extending the drying time for the on-line column, saving purge air (energy).
Once the dewpoint of the air leaving the dryer is equal to the ECO set point or the moisture override period has been reached (default 30
minutes), the dryer will change over and the fully saturated bed will be regenerated.
A dewpoint value higher (wetter) than the dewpoint alarm set point will place the dryer into dewpoint alarm mode."
Dewpoint Alarm
Should the outlet dewpoint drop below the Dewpoint Alarm Set Point, the dewpoint displayed will flash and the fault alarm symbol will be
displayed. The generic fault relay will also change state.
The dryer will continue to cycle normally during dewpoint alarm. Once the dewpoint is higher than the alarm set point, the dryer display and fault
relay will return to normal.
3.5.7 Temperature Units
The dryer display can be configured to show outlet dewpoint in °C or °F and can be set using the dipswitch configuration below.
Dipswitch Array (2)
DIL
Switch
Function
OFF
ON
Switch 5 Dewpoint Setpoint 1
Switch 6 Dewpoint Setpoint 3
Dipswitch Array (2)
DIL
Switch
Function
OFF
ON
Switch 3
Temperature unit
selection
o
C
o
F
-20 C
-40 C
-70 C
Summary of Contents for CDAS HL 050 Series
Page 2: ......
Page 4: ......
Page 36: ...32 8 Schematics Pneumatic Schematic 008730000 ...
Page 37: ...33 Wiring Diagram 008730002 ...
Page 38: ...34 ...
Page 40: ......
Page 72: ...68 8 Schema Persluchtschema 008730000 ...
Page 73: ...69 Bedradingsdiagram 008730002 ...
Page 74: ...70 ...
Page 76: ......
Page 108: ...104 8 Anschlusspläne Pneumatik Schemazeichnung 008730000 ...
Page 109: ...105 Schaltplan 008730002 ...
Page 110: ...106 ...
Page 112: ......
Page 144: ...140 8 Schéma Schémas pneumatiques 008730000 ...
Page 145: ...141 Schéma de câblage 008730002 ...
Page 146: ...142 ...
Page 148: ......
Page 180: ...176 8 Scheman Pneumatikschema 008730000 ...
Page 181: ...177 Kopplingsschema 008730002 ...
Page 182: ...178 ...
Page 184: ......
Page 216: ...212 8 Skjemaer Pneumatisk skjema 008730000 ...
Page 217: ...213 Koblingsskjema 008730002 ...
Page 218: ...214 ...
Page 220: ......
Page 252: ...248 8 Skema Pneumatisk skema 008730000 ...
Page 253: ...249 Ledningsdiagram 008730002 ...
Page 254: ...250 ...
Page 256: ......
Page 288: ...284 8 Diagramas Diagrama neumático 008730000 ...
Page 289: ...285 Diagramas del cableado 008730002 ...
Page 290: ...286 ...
Page 292: ......
Page 324: ...320 8 Schemi Schema pneumatico 008730000 ...
Page 325: ...321 Schema di cablaggio 008730002 ...
Page 326: ...322 ...
Page 328: ......
Page 360: ...356 8 Schematy Schemat pneumatyczny 008730000 ...
Page 361: ...357 Schemat okablowania 008730002 ...
Page 362: ...358 ...
Page 364: ......
Page 374: ...370 2 7 Parker domnick hunter 2 7 1 2 7 2 A B C ...
Page 379: ...375 3 3 3 3 1 3 3 2 500 20 750 29 5 3 4 3 4 1 ...
Page 385: ...381 3 5 8 CDAS OFAS CDAS OFAS DIP 008730000 8 _ 3 6 1 2 3 4 DIP 1 DIL 7 ...
Page 387: ...383 4 1 2 _ _ _ _ ERR _ ECO ECO ECO MODBUS ECO ...
Page 388: ...384 4 2 1 2 3 4 5 4 3 1 2 3 _ MODBUS ...
Page 389: ...385 5 5 1 _ _ 3 _ 6 _ 12 _ 60 _ POWER ON STATUS FAULT OFAS ...
Page 393: ...389 6 6 1 _ _ _ Parker 12 350 Parker Parker Parker Parker ...
Page 394: ...390 6 2 6 3 _ 12 Parker ...
Page 396: ...392 8 008730000 ...
Page 397: ...393 008730002 ...