Parker Hannifin
Troubleshooting 153
PROBLEM
CAUSE / VERIFICATION
SOLUTION
Ethernet Communication
Communication Error:
11003
Using straight through (patch) Ethernet cable.
Change to a crossover Ethernet cable.
Communication Error:
11010
Using crossover Ethernet cable through router/hub.
Change to a straight through Ethernet cable.
Communication Error:
11003
Wrong computer IP address and/or subnet mask.
Change IP address of computer in Ethernet card settings.
Communication Error:
10061
Same IP address as ACR9000.
Change IP address of computer in Ethernet card settings.
Communication Error:
11010
Wrong IP address configured in ACR-View
communication window.
Enter in correct ACR9000 IP address.
PCI Card Communication
Controller is not
present in Windows
Device Manager
AMCSPCI driver card not installed correctly.
Reinsert the ACR1505 or ACR8020.
Check for compatible operating systems.
Communication Error:
17080
ACR-View cannot establish communication.
Check PCI communications.
Shut down computer and restart.
Operation
Check if 24 VDC is applied to the Motion Enable Input.
Motion enable input is open.
Verify by checking Status Panels
Æ
Bit Status
Æ
Miscellaneous Control Flags.
Bit 5646 indicates status of 24VDC Motion Enable Input.
Bit 5645 indicates if Motion Enable Input has been latched.
If both 5645 and 5646 are set, reapply 24V to Motion Enable
Input.
If only 5645, then SET 5647 to clear 5645 latch.
For Encoder Signal Fault: Check for incorrect termination.
Noise in the system can cause missed and/or false encoder
feedback values.
Encoder signal fault and/or encoder signal is lost.
Verify by checking Status Panels
Æ
Bit Status
Æ
Encoder Flags.
NOTE:
Each encoder input has specific flag sets.
For Encoder Signal Lost: Check feedback cables.
Drive will not enable
Amplifier/drive is not powered on.
Check if power is applied to the amplifier/drive.