DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
76 (125)
DOC-0017-03-EN-B 04.04.2023
Application ‘1’: Standard (Basic Speed Control)
This Application is ideal for general purpose applications. It provides push-button or switched start/stop
control. The setpoint is the sum of the two analogue inputs AIN1 and AIN2, providing Speed Se
Speed Trim capability.
Configuration Setup:
RL1A
110-230Vac (or 24Vdc) voltage supply
RL1B
Healthy:
Relay output (to lamp)
TH1
Motor Thermistor ‘+’ connection
TH2
Motor Thermistor ‘-’ connection
AI1
Remote Setpoint (%) – input 1:
0-10V variable input (from potentiometer)
AI2
Remote Setpoint ‘Trim’ (%) – input 2:
4-20mA variable input (from current source)
AO1
Speed Demand (%):
0-10V variable output (to voltmeter)
AO2
Value = 100%:
0-10V variable output (+10V fixed reference voltage)
DX1
Run Forward:
24V digital input
DX2
Remote Reverse:
24V digital input
DX3
Jog:
24V digital input
DI4
Not Stop:
24V digital input
DI5
Not Coast Stop:
24V digital input
STO
STO
DISABLED
(drive operational)
V
↑
V
S