DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
108 (125)
DOC-0017-03-EN-B 04.04.2023
Recommended Wire Sizes
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated
(75ºC) copper conductors.
The wire sizes allow for an ampacity of 125% of the rated input and output amperes for motor branch-circuit
conductors as specified in NEC/NFPA-70.
Refer to ‘Chapter 6: Installation’ for recommended wire sizes.
Field Wiring Temperature Rating
Use minimum 75°C Copper conductors.