6 Maintenance
a) The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the maintenance
performed;
b) when requesting assistance or spare parts, identify the machine
(model and serial number) by reading the data plate located on the
unit.
6.1 General instructions
!
Before any maintenance, make sure:
• the pneumatic circuit is no longer pressurized;
• the dryer is disconnected from the main power supply
.
Y
Always use the Manufacturer’s original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunctioning
Y
In case of refrigerant leakage, contact qualifi ed and authorized per-
sonnel.
Y
The Schrader valve must only be used in case of machine malfunc-
tion: otherwise any damage caused by incorrect refrigerant charging will
not be covered by the warranty.
6.2 Refrigerant.
Charging: any damage caused by incorrect refrigerant replacement car-
ried out by unauthorized personnel will not be covered by the warranty.
Z
Y
Th
e equipment contains fl uorinated greenhouse
gases.
At normal temperature and pressure, the R407c refrigerant is a colour-
less gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid accord-
ing to Directive PED 2014/68/EU)
GWP (Global Warming Potential) = 1774.
!
In case of refrigerant leakage, ventilate the room.
6.3 Preventive Maintenance Programme
To guarantee lasting maximum dryer effi ciency and reliability
Maintenance
Activity Description
Maintenance Interval
(standard operating condi-
tions)
Activity
Check
Service
Daily
W
eekly
4 Months
12 Months
36 Months
Check POWER ON indicator is lit.
Check control panel indicators.
Check condensate drain.
Clean condenser fi ns.
Check electrical absorption.
Depressurize the dryer. Complete
drain maintenance.
Depressurize the dryer. Replace pre-
and post-fi lter elements.
Dryer maintenance kit.
The following are available (see par. 8.4):
a) 3 years preventive maintenance kits;
b) service kit
• compressor kits;
• fan kits;
• hot gas valve kits;
c) individual spare parts.
6.4 Dismantling
The refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
The refrigerant fl uid is recovered before fi nal scrapping of the equipment
((UE) No 517/2014 art.4.4).
%
Recycling Disposal
Z
structural work
steel/epoxy-polyester resins
exchanger
aluminium
pipes/headers
copper/aluminium/carbon steel
drain
polyamide
exchanger insulation
EPS (sintered polystyrene)
pipe insulation
synthetic rubber
compressor
steel/copper/aluminium/oil
condenser
steel/copper/aluminium
refrigerant
R407c
valves
brass
electrical cables
copper/PVC
Summary of Contents for Polestar-Smart PSH030
Page 2: ......
Page 8: ...Italiano 6 6 PSH 030 090 ...
Page 14: ...English 6 6 PSH 030 090 ...
Page 20: ...Español 6 6 PSH 030 090 ...
Page 26: ...Français 6 6 PSH 030 090 ...
Page 32: ...Deutsch 6 6 PSH 030 090 ...
Page 38: ...Português 6 6 PSH 030 090 ...
Page 44: ...Svenska 6 6 PSH 030 090 ...
Page 50: ...Suomi 6 6 PSH 030 090 ...
Page 56: ...Norsk 6 6 PSH 030 090 ...
Page 62: ...Nederlands 6 6 PSH 030 090 ...
Page 68: ...Dansk 6 6 PSH 030 090 ...
Page 74: ...Polski 6 6 PSH 030 090 ...
Page 80: ...Česky 6 6 PSH 030 090 ...
Page 86: ...Magyar 6 6 PSH 030 090 ...
Page 92: ...Ελληνικά 6 6 PSH 030 090 ...
Page 98: ...Русский 6 6 PSH 030 090 ...
Page 107: ...8 5 EXPLODED DRAWING 9 PSH 030 090 15 12 34 2 9 1 8 3 5 4 A B1 ...
Page 108: ...8 6 DIMENSIONAL DRAWING 10 PSH 030 090 inches mm ...
Page 109: ...8 7 REFRIGERANT CIRCUIT 11 PSH 030 090 Only 065 090 models ...
Page 110: ...8 8 WIRING DIAGRAM 12 PSH 030 090 Sheet 1 of 4 ...
Page 111: ...8 8 WIRING DIAGRAM 13 PSH 030 090 Sheet 2 of 4 ...
Page 112: ...8 8 WIRING DIAGRAM 14 PSH 030 090 Sheet 3 of 4 315mA 250V ...
Page 113: ...8 8 WIRING DIAGRAM REMOTE ALARM OPTIONAL 15 PSH 030 090 Sheet 4 of 4 ...
Page 114: ......
Page 115: ......