Esprit 728 Ultra & 738 Ultra - 13 - Programming Guide
Advanced Technology Zone (ATZ) Connections
Other Connection Diagrams
Figure 8: N.C. Contacts, without EOL Resistor
Figure 9: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Figure 10: N.C. Contacts, with EOL Resistor, with Tamper and Wire
Fault Recognition (UL/cUL)
Figure 11: Parallel Wiring
Figure 12: Connecting Keypad Zone(s)
Address 088, [
MEM
] = “ON” (EOL resistor disabled)
[0] = “OFF”
[
STAY
] = “OFF”
Address 090, [8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Tamper/Wire Fault disabled.
Address 088, [
MEM
] = “ON” (EOL resistor disabled)
[0] = (See Tamper/Wire Fault definitions on
[
STAY
] = page 10.)
Address 090, [8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Address 088, [
MEM
] = “OFF” (EOL resistor enabled)
[0] = (See Tamper/Wire Fault definitions on
[
STAY
] = page 10.)
Address 090, [8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Address 088, [
MEM
] = “OFF” (EOL resistor enabled)
[0] = “OFF”
[
STAY
] = “OFF”
Address 090, [8] = “ON” (ATZ enabled)
[7] = “ON” (ATZ wiring in parallel)
Tamper/Wire Fault disabled.