Esprit 728 Ultra & 738 Ultra  - 17 -   Programming Guide

Power Down Reset

Performing a power down reset will set the Installer and Master codes to factory default. Values entered at addresses 008 to 043062 to 
124, 300 to 527 and all user codes will be set to factory defaults. Programmed values at addresses 003 to 007 do not change. To perform 
a reset, the installer lock must be disabled. To perform a power down reset perform the following:

1.

Verify installer lock is disabled.

2.

Remove the battery and AC power from the control panel.

3.

Remove all connected wires and devices from the PGM (PGM1 for 738 Ultra) and zone 1 terminals.

4.

Short the PGM (PGM1 for 738 Ultra) and zone 1 terminals with a wire.

5.

Reconnect the AC and battery power to the control panel.

6.

Wait for 10 seconds and remove the wire. 

Figure 19: Power Down Reset for 728 Ultra

 

or 738 Ultra  

Warranty

Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as 
specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for 
a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not 
manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to 
operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. Returns 
must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct 
or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or 
otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold. 

Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this product signifies 
your acceptance of this warranty. 

BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.

© 2003-2006 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more of the following US patents may apply: 6215399, 
6111256, 5751803, 5721542, 5287111, 5119069, 5077549, 5920259 and 5886632. Canadian and international patents may also apply. Esprit is a trademark or registered 
trademark of Paradox Security Systems Ltd. or its affiliates in Canada, the United States and/or other countries. 

1. Remove power.
2. Remove all connected wires and devices from the 

PGM (PGM1 for 738 Ultra) and zone 1 terminals.

3. Short the PGM (PGM1 for 738 Ultra) and zone 1 

terminals.

4. Reconnect power.
5. Wait 10 seconds and remove wire.

Summary of Contents for Esprit 728 Ultra

Page 1: ...728 Ultra With ATZ 738 Ultra No ATZ 738 Ultra With ATZ Control Panel Input 1 Zone 1 Zones 1 2 Zone 1 Zones 1 9 Input 2 Zone 2 Zones 3 4 Zone 2 Zones 2 10 Input 3 Zone 3 Zones 5 6 Zone 3 Zones 3 11 Inp...

Page 2: ...Auxiliary Current 11 Fire Loop Trouble Table 4 Hex Programming Method 1 Press ENTER INSTALLER CODE default 728 Ultra 282828 738 Ultra 383838 2 The ENTER key will flash indicating you are in programmi...

Page 3: ...ts are programmed 02 __ __ __ __ __ __ __ __ 03 __ __ __ __ __ __ __ __ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Monitoring Station Telephone Number 1 View at addresses 016 to 023 Streamline Section Str...

Page 4: ...SOUNDER RELAY TROUBLE 2 8 116 DUCT 2ND 8 321 BELL 1 TROUBLE 2 9 117 FLAME 2ND 9 323 ALARM RELAY TROUBLE 2 0 118 NEAR ALARM 2ND 0 350 COMMUNICATION TROUBLE 2 STAY 120 PANIC ALARM 2ND STAY 351 TELCO 1...

Page 5: ...___ ___ User Code 8 309 ___ ___ User Code 32 333 ___ ___ User Code 9 310 ___ ___ User Code 33 334 ___ ___ User Code 10 311 ___ ___ User Code 34 335 ___ ___ User Code 11 312 ___ ___ User Code 35 336 __...

Page 6: ...93 ___ ___ User Code 27 378 ___ ___ User Code 43 394 ___ ___ User Code 28 379 ___ ___ User Code 44 395 ___ ___ User Code 45 396 ___ ___ User Code 46 397 ___ ___ User Code 47 398 ___ ___ User Code 48 D...

Page 7: ...ddress Streamline Section Data Description Address ___ ___ Max aux current 496 ___ ___ Fire loop trouble 500 ___ ___ Bell disconnect max bell current 497 ___ ___ Timer loss 501 ___ ___ Battery disconn...

Page 8: ...est report between 000 and 059 738 Ultra only minutes If address 046 255 and the system is disarmed Disarmed Test Report between 001 and 255 000 049 ___ ___ ___ seconds Exit delay 60 seconds 050 ___ _...

Page 9: ...ess the ENTER key to accept there will be a confirmation beep indicating the options have been accepted The ENTER key will flash to indicate that the software is awaiting the next address entry 5 Retu...

Page 10: ...cy timer in days U 3 N In hours Restrict arming on battery failure U 4 N Enabled Restrict arming on tamper trouble U 5 N Enabled No tamper bypass U 6 N Tamper follows zone bypass definition Zone doubl...

Page 11: ...N N N N N N SYSTEM A STAY if ON zone is armed on Stay or System A arming Zone 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 116 116 N N N N N N N N N N N N 118 N N N N N N SYSTEM B if ON zone is armed...

Page 12: ...ire Fault Recognition UL cUL Address 088 MEM ON EOL resistor disabled 0 OFF STAY OFF Address 090 8 OFF ATZ disabled Tamper Wire Fault disabled Address 088 MEM OFF EOL resistor enabled 0 OFF STAY OFF A...

Page 13: ...dress 088 MEM ON EOL resistor disabled 0 OFF STAY OFF Address 090 8 ON ATZ enabled 7 OFF ATZ wiring in serial Tamper Wire Fault disabled Address 088 MEM ON EOL resistor disabled 0 See Tamper Wire Faul...

Page 14: ...e 2 wire smoke detector and zone 6 will be disabled automatically 2 Wire Smoke Detector Fire Reset Simultaneously press and hold for 3 seconds the ENTER and CLEAR keys on any keypad to conduct a 30 se...

Page 15: ...he system AUX POWER 450mA maximum UL cUL 250mA maximum for 24Hr Stand by To connect additional wiring to the auxiliary power use the red and the black keypad connectors AUX power will shut down if cur...

Page 16: ...ble Acid Lead or Gel Cell Backup Battery Improper connection may result in damage to the system AUX POWER 500mA maximum 250mA maximum for 24Hr Stand by To connect additional wiring to the auxiliary po...

Page 17: ...sulting from the product s inability to operate Seller obligation and liability under this warranty is expressly limited to repairing or replacing at Seller s option any product not meeting the specif...

Page 18: ...Notes...

Page 19: ......

Page 20: ...paradox com PRINTED IN CANADA 07 2007 7X8ULT EP04...

Reviews: