INSTRUCTIONS CM408F
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 18 of 24
Vertical Patch Panel Bracket Installation
Position vertical support of vertical patch panel bracket so that it nestles behind flange of finger bracket. Mounting points are located on the
outside of finger bracket. Secure vertical patch panel bracket to Net-SERV finger bracket with (2) #12-24 hex head screws into tapped holes
of vertical support of vertical patch panel as shown. Screws are to pass through slots in finger bracket to engage vertical patch panel bracket
and allow for vertical adjustment of bracket.
NOTES
-SVPPB to be used with finger bracket only (700mm/28”)
-Recommend use with Panduit Pan-Net and Quick-Net (1) Rack Unit Patch Panels
-(3) SVPPB may be fitted to a 42 RU (700mm/28”) cabinet
-(4) SVPPB may be fitted to a 45 RU (700mm/28”) cabinet
#12-24 Hex
Head Screw
Vertical Patch Panel
Bracket (SVPPB)
(Vertical support nestles
behind flange of finger rail)
#12-24 Hex
Head Screw
Bracket
Installed