65
13.1.6. Low Pressure Protection Control
• Purpose:
- To protect the system operation.
- Detection period:
- After compressor on for 5 minutes.
- Detection conditions:
- When detection of Tem above 26 C.
- Calculation of average evaporation temperature (Tem).
- Use outdoor piping temperature sensor.
Tem use the value calculated for discharge temperature setting value.
- After detection:
- Compressor stops restart again after 3 mins.
- When abnormalities continuously generated 60 times within 480 minutes, system stops.
- Protection operation is prohibited.
- Error H42 will be displayed.
13.1.7. High pressure sensor control
• Purpose:
- To protect the system operation.
• Detection period:
- After compressor on for 1 minute.
• Detection conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
• After detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.8. Outside Temperature Current Control
13.1.9. Extreme Low Temperature Control
• Purpose:
- To improve the compressor reliablity during cold start and after deice when running in extreme low outdoor temperature
-20 C.
Starting condition:
1. Heating operation
2. Outdoor air tempearture < -10 C
3. Actual frequency
50Hz
4. Compressor discharge temperature < 20 C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancelation condition:
- starting condition not fulfill.
- Cancel the extreme low temperature control when compressor discharge sensor 60 C
Summary of Contents for WH-SXC09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Page 23: ...23 8 1 2 WH SXC12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Page 26: ...26 9 1 2 WH SXC12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Page 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Page 125: ...125 ...