66
13.1.10. Crank case heater control
• Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
• Control content:
a. Trigger heater START conditon
• when the outdoor air temperature is 13 C or below, and discharge temperature is 13.2 C or below.
b. Resetting heater STOP condition
1. when the outdoor air temperature exceeds entry condition (15 C)
2. when the discharge temperature exceeds entry condition (20.2 C)
13.2. Protection Control For Heating Operation
13.2.1. Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14 C in order to avoid compressor
overloading.
13.2.2. Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
13.3. Protection Control For Cooling Operation
13.3.1. Outdoor Air Temperature Control
• The Compressor operating frequency is regulated in accordance to The outdoor air temperature as shown in The diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air Temperature.
13.3.2. Freeze Prevention Control 1
1. When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C.
3. Indoor heat exchanger freeze prevention (H99) will memory in error history.
Summary of Contents for WH-SXC09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Page 23: ...23 8 1 2 WH SXC12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Page 26: ...26 9 1 2 WH SXC12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Page 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Page 125: ...125 ...