35
11.3.3.5. Drain Elbow and Hose Installation
• Fix the drain elbow and packing to the bottom of indoor
unit, as show in below illustration.
• Use inner diameter 17 mm drain hose in the market.
• This hose must to be installed in a continuously downward
direction and in a frost-free environment.
• Do not insert this hose into sewage hose or cleaning hose
that may generate ammonia gas sulfuric gas etc.
• If necessary, use hose clamp to further tighten the hose at
drain hose connector to prevent it leakage.
• The water may drip from drain hose. Therefore must ensure
the outlet of the hose is always not closed or blocked.
11.3.4. CONNECT THE CABLE TO THE INDOOR UNIT
1. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 4.0 or 6.0 mm
2
flexible cord, type designation 60245 IEC 57 or heavier cord.
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor unit’s respectively.
• Earth wire shall be longer than the other wires as shown in the figure for the electrical safety in case of the slipping out of the
cord from the Holder (Clamper).
2. Cable connection to the power supply through isolating device (Disconnecting means).
• Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
• Connect the approved polychloroprene sheathed power supply 1 cord (3 4.0 or 6.0 mm
2
) and power supply 2 cord (3 x
4.0 mm
2
) and power supply 3 cord (3 1.5 mm
2
) (Not applicable for SXC09D3E5), type designation 60245 IEC 57 or
heavier cord to the terminal board, and to the other end of the cord to isolating device (Disconnecting means).
3. To avoid cable and cord harmed by sharp edge, cable and cord must go through bushing (located at the bottom of indoor unit)
before carry out electrical connection. The bushing must be used and must not take off.
Connecting with external device (optional)
1.
All connections
shall
follow to the local national wiring standard.
2. It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
3. Maximum output power of booster heater shall be
3 kW. Booster Heater’s cord must be (3 min 1.5 mm
2
), of type
designation 60245 IEC 57 or heavier.
4. Two-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve’s cable shall be
(3 min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 3VA.
5. Three-Way Valve shall be spring and electronic type. Valve’s cable shall be (3 min 0.5 mm
2
), of type designation 60245 IEC
57 or heavier, or similarly double insulation sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is OFF.
- Maximum load for the valve is 3VA.
6. Receiver shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table for details. Receiver’s cable
must be (4 or 3 min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable. (connection refer to
Diagram 5.2).
7. Tank OLP’s cable must be (2 min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal no. 13 and 14.
8. Tank Sensor shall be resistance type, please refer to Graph 5.1 for the characteristic and details of sensor. Its cable shall be
(2 min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-sheathed or rubber-sheathed cable.
9. External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to Diagram 5.3). Its
cable must be (2 min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no. 17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
10. Solar Three-way Valve’s cable shall be (3 min 0.5 mm
2
), double insulation layer PVC-sheathed or rubber-sheathed cable.
Summary of Contents for WH-SXC09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Page 23: ...23 8 1 2 WH SXC12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Page 26: ...26 9 1 2 WH SXC12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Page 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Page 125: ...125 ...