67
14 Servicing Mode
14.1. Test Run
1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction.
2. Set ON to the indoor unit and RCCB/ELCB. Then, for control panel’s operation please refers to air-to-water heatpump’s
operation instruction.
3. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.2 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water pump
speed cannot solve the problem, contact your local authorized dealer.
14.2. Proper Pump Down Procedure
1. Make sure the OFF/ON control panel LED is OFF (no operation).
2. Press the “PUMPDW” switch on control panel to begin PUMP DOWN mode. Operate the system in PUMP DOWN mode for
10 ~ 15 minutes.
3. After 10-15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10 C)), fully close 2 way valve.
4. After 3 minutes, fully close 3 way valve.
5. Press the “OFF/ON” switch on control panel to stop PUMP DOWN mode.
6. Remove the refrigerant piping.
14.3. How To Adjust Water Flow Rate
• Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum.
• The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is moderate speed
(II). However, please ensure the minimum flow rate cannot be less than 18L/min. Adjust it to high speed (III) and slow speed (I) if
necessary (e.g. reduce the noise of running water).
Below graph shown the external static pressure (kPa) versus water flow rate (l/min).
• Flow rate characteristic of indoor unit is as per above mentioned.
14.4. Expansion Vessel Pre Pressure Checking
• Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this indoor unit.
• Total amount of water in system should be below 200L.
(Note: This amount of water is not include the tank unit volume)
• If total amount of water is over 200L, please add expansion vessel.
• Please keep the installation height difference of system water circuit within 7m.
(Inner volume of same indoor unit is about 5L)
Summary of Contents for WH-SXC09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Page 23: ...23 8 1 2 WH SXC12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Page 26: ...26 9 1 2 WH SXC12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Page 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Page 125: ...125 ...