58
12.13. Quiet Operation
• Purpose:
- To provide quiet operation compare to normal operation by reduces outdoor unit noise.
• Starting condition:
1. When quiet button is presses.
2. When quiet request ON time by weekly timer (Refer to control panel.)
• When any of above mentioned condition is achieved, this control is activated.
New target FM speed = Present target FM speed - 80 rpm
Minimum target FM speed = 200 rpm
• Cancellation condition:
1. Cancel by press quiet button
2. Stop by OFF/ON button
3. When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
12.14. Solar operation (Optional)
12.14.1. Solar operation:
• Control according to preset whether Solar Priority is set or not.
• When tank connection is NOT set at SETTING mode, Solar operation is disabled.
• When Pump A (from Solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is
requested ON (Refer to figure below).
12.14.2. Solar operation control
When solar priority is SET
1. Operation condition:
• Solar pump operates if all of the following conditions are fulfilled:-
i) Power On. (regardless operation ON or OFF)
ii) There is operation request from Solar pump station.
iii) Tank hot water temp is below solar on upper limit temp [EEPROM 1 : 70] C.
2. Stop condition:
• Solar pump stops operating when:-
í) No power supply to unit
OR
ii) There is
NO
operation request from Solar pump station
OR
iii) Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77] C.
* heat pump OFF OR operate to room side when solar pump operate during solar priority set
* booster heater OFF when solar pump operate during solar priority set
Summary of Contents for WH-SXC09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up The Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Page 21: ...21 7 2 WH UX12DE5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXC09D3E5 ...
Page 23: ...23 8 1 2 WH SXC12D6E5 ...
Page 24: ...24 8 2 Outdoor Unit ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXC09D3E5 ...
Page 26: ...26 9 1 2 WH SXC12D6E5 ...
Page 27: ...27 9 2 Outdoor Unit ...
Page 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Page 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 45: ...45 Solar Priority is Set Solar Priority is Not Set ...
Page 51: ...51 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Page 60: ...60 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 61: ...61 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 110: ...110 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 124: ...124 19 2 WH UX09DE5 WH UX12DE5 ...
Page 125: ...125 ...