background image

48

Cleaning instructions

Regular Checks

Indoor unit

• 

Do not splash water directly.

Wipe the unit gently with a soft dry cloth.

• 

Please ensure the front plate cover 

is put back in place after servicing or 

maintenance.

To ensure optimal performance of the system, cleaning has to be carried out at regular intervals.

Consult an authorised dealer.

• 

Disconnect the power supply before cleaning.

• 

Do not use benzine, thinner or scouring powder.

• 

Use only soap (   pH7) or neutral household detergent.

• 

Do not use water hotter than 40 °C.

Safety relief valve

SDC, SXC Hot water heater has one safety valve for the 

(CIRCUIT).

• 

The CIRCUIT’s safety relief valve must be completely 

closed and must not normally release any water.

• 

The functioning of the safety relief valve should be 

checked regularly. You can 

fi

 nd the safety valve behind 

the inspection cover on the front.

Perform the checks as follows:

1. Open the valve.

2. Check that water 

fl

 ows through the valve.

3. Close the valve.

4. Check the system pressure, top up if required.

Water pressure check

• 

Ensure that the water pressure is between 

0.5 bar and 3.0 bar.

• 

In case the water pressure is out of the 

above range, consult an authorised dealer.

• 

Water pressure can be checked through 

following method:-

Go to System check > System information > 

Water pressure

Water 

fi

 lter

• 

Clean the water 

fi

 lter at least once a year. Failure to do 

so may cause the 

fi

 lter to clog up, which may lead to 

system breakdown. Consult an authorised dealer.

• 

Please also remove dust on the magnet.

Outdoor unit

• 

Do not obstruct the air inlet and outlet vents. Failure 

to do so may result in low performance or system 

breakdown. Remove any obstruction to assure the 

ventilation.

• 

When it snows, clean and remove snow around the 

outdoor unit to prevent the air inlet and outlet vents from 

being covered with snow.

Tips: For extended non-use

• 

The water inside the Tank should be drained.

• 

Disconnect the power supply.

Info: Non serviceable criteria

Disconnect the power supply

then please consult an authorised dealer under the 

following conditions:

• 

Abnormal noise during operation.

• 

Water/foreign particles have entered the Remote 

Controller.

• 

Water leaks from the indoor unit.

• 

Circuit breaker switches off frequently.

• 

Power cord becomes excessively warm.

Summary of Contents for WH-SDC12K6E5

Page 1: ...oor Unit Outdoor Unit WH SDC0309K3E5 WH SDC0309K6E5 WH UDZ03KE5 WH UDZ05KE5 WH UDZ07KE5 WH UDZ09KE5 WH SDC12K6E5 WH UDZ12KE5 WH SDC09K3E8 WH SDC09K9E8 WH SDC12K9E8 WH SDC16K9E8 WH UDZ09KE8 WH UDZ09KE8...

Page 2: ...Optional PCB connectivity 5 2 Zone Sensor 5 3 Heater capacity 5 4 Anti freezing 5 5 DHW capacity 5 6 Buffer tank connection 5 7 Base pan heater 5 8 Alternative outdoor sensor 5 9 Bivalent connection 5...

Page 3: ...Above Ambient 10 C 3 5 20 Outdoor ambient temperature C Min Max 20 35 WH UDZ03KE5 25 35 WH UDZ05 07 09 12KE5 WH UDZ09 12 16KE8 28 35 WH UXZ series 10 43 When the outdoor temperature is out of the ran...

Page 4: ...een given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall no...

Page 5: ...check RCCB ELCB operation regularly especially after installation inspection and maintenance RCCB ELCB malfunction may result in electric shock and or fire It is strongly recommended that Install Res...

Page 6: ...nit and degrade the insulation This may cause an electric shock Prevent water leakage by ensuring drainage pipe is Connected properly Kept clear of gutters and containers or Not immersed in water Afte...

Page 7: ...ls Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a n...

Page 8: ...ledge of and skills in handling flammable refrigerants personal protective equipment refrigerant leakage prevention handling of cylinders charging leak detection recovery and disposal and c Able to un...

Page 9: ...th national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and cer...

Page 10: ...uding respiratory protection as conditions warrant Keep all sources of ignition and hot metal surfaces away 2 3 Checking for presence of refrigerant The area shall be checked with an appropriate refri...

Page 11: ...ased refrigerant and preferably expel it externally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to...

Page 12: ...airs to sealed components During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is abso...

Page 13: ...ms No leaks shall be detected using detection equipment with sensitivity to detect leakage of 5g year of refrigerant or better under a pressure of at least 0 25 times the maximum allowable pressure 1...

Page 14: ...ons on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available OFN oxygen free nitrogen type of ine...

Page 15: ...refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with...

Page 16: ...le refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before us...

Page 17: ...Back button Returns to the previous screen 3 LCD Display Actual Dark background with white icons 4 Main Menu button For function setup 5 ON OFF button Starts Stops operation 6 Operation indicator Illu...

Page 18: ...when the water tank is installed The direction icons point to the currently active mode Room operation Tank operation Deice operation B Operation icons The status of operation is displayed Icon will...

Page 19: ...0 am 2022 1 Select with or how to display the time either 24h or am pm format for example 15 00 or 3 00 pm 2 Press to confirm the selection 3 Use and to select year month day hour and minutes Select a...

Page 20: ...the setting according to the instructions displayed at the bottom of the screen The icons refer to each selection key Quick Menu Force DHW Powerful Quiet Force Heater Weekly Timer Force Defrost Error...

Page 21: ...f operation mode should change back to the previous memorized status Powerful Select this icon to operate the heating cooling system powerfully Press to confirm your selection The powerful operation s...

Page 22: ...tes at level 2 The Quiet mode operates at level 3 Level 3 is the most quiet mode Select this to set a timer for the Quiet mode operation After 1 sec delay Select Yes Select Yes using buttons Select pa...

Page 23: ...nfirm your selection The Force Heater mode starts approximately 1 minute after is pressed Force Heater is turned off Force Heater is turned on Note Force Heater is disabled whenever operation is alrea...

Page 24: ...Timer setup Select the day s which you wish to edit using buttons If all 6 patterns are not preset this screen will be displayed 1 2 3 4 5 6 1 Select pattern 1 6 2 Set the hour and minutes of the Tim...

Page 25: ...ock Select to lock the Remote Controller Press to confirm your selection When the mode has been accepted below screen will be displayed Select Yes The Main Screen will be locked If No is selected the...

Page 26: ...p 1 1 Weekly timer Once the weekly timer is set up User can edit from Quick Menu To set up to 6 patterns of operation on a daily basis Disabled if Heat Cool SW is select Yes or if Force Heater is on T...

Page 27: ...oritize on providing required capacity at the same time Sound Capacity Sound 1 5 Room heater To set the room heater ON or OFF OFF 1 6 Tank heater To set the tank heater ON or OFF OFF 1 7 Sterilization...

Page 28: ...V and may differ from value measured by precise equipment 2 2 System information Shows all system information in each area Actual system information of 11 items Inlet Outlet Zone 1 Zone 2 Tank Buffer...

Page 29: ...etrieve RC No Confirm 10 34am Mon RC 1 3 2 Touch sound Turns the operation sound ON OFF ON 3 3 LCD contrast Sets the screen contrast 3 3 4 Backlight Sets the duration of screen backlight 1 min 3 5 Bac...

Page 30: ...AIS DEUTSCH ITALIANO ESPA OL DANISH SWEDISH NORWEGIAN POLISH CZECH NEDERLANDS T RK E SUOMI MAGYAR SLOVEN INA HRVATSKI LIETUVI PORTUGU S EESTI LATVIE U ROM N SHQIP SLOVEN INA 3 9 Unlock password 4 digi...

Page 31: ...Heat Cool SW 5 2 Zone Sensor To select the sensors and to select either 1 zone or 2 zone system Zone After selecting 1 or 2 zone system proceed to the selection of room or swimming pool If the swimmi...

Page 32: ...e 0 C 10 C Steps 1 C Select Confirm 10 34am Mon 5 C 5 7 Base pan heater To select whether or not optional base pan heater is connected Type A The base pan heater activates only during deice operation...

Page 33: ...C Set outdoor temperature for turn ON Bivalent connection Yes After selecting the outdoor temperature Control pattern Alternative Parallel Advanced parallel Select advanced parallel for bivalent use...

Page 34: ...t Pump OFF Boiler OFF Short Open Heat Pump ON Boiler OFF Open Short Heat Pump OFF Boiler ON Short Short Heat Pump ON Boiler ON To do settings related to electricity and boiler so that unit is able to...

Page 35: ...r electricity price Set the price according to value provided by electrical supply company Figure 1 Bivalent connection 10 34am Mon Select 0 0 Range 0 999 9 kWh Steps 0 1 kWh Electricity price 1 0 0 0...

Page 36: ...Dec Steps 1month Select Confirm 10 34am Mon Dec Yes Smart After selecting for the external pump Schedule Schedule setting Start time Pattern 1 3 00am Start time Pattern 2 9 00am Start time Pattern 3...

Page 37: ...e previous set value of Electricity price 1 to Electricity price 10 When the price is set to 0 the electricity price will be treated as 0 0 kWh It is for the convenience of installer when 0 0 is the d...

Page 38: ...re 5 C Set Antifreeze temperature Yes After selecting the tank T ON temperature T OFF temperature After setting the antifreeze temperature 80 C Set Hi limit 5 12 External error signal No 5 13 Demand c...

Page 39: ...Manual 5 20 Defrost signal To turn on defrost signal to stop fan coil during defrost operation If defrost signal set to yes bivalent function will not available to use No 5 21 Pump flowrate To set va...

Page 40: ...is connected It is to measure energy generation of heat pump unit during heating cooling and DHW operation one generation meter system or during heating and cooling only two generation meter system T...

Page 41: ...data displayed on the remote controller is obtained through heat pump s internal calculation If Approx is NOT shown on Energy Monitor display data displayed on the remote controller is obtained by Ex...

Page 42: ...urve X axis 5 C 15 C Y axis 55 C 35 C Input the 4 temperature points 2 on horizontal X axis 2 on vertical Y axis Temperature range X axis 20 C 15 C Y axis See below Temperature range for the Y axis in...

Page 43: ...turn on Heater ON OFF Water temperature for heater ON 4 C Setting of water temperature to turn on from water set temperature Heater ON OFF Water temperature for heater OFF 2 C Setting of water tempera...

Page 44: ...zone system is selected temperature set point must input for Zone 2 Zone 1 and Zone 2 will not appear on the display if only 1 zone system T for cooling ON 5 C Set T for cooling ON This setting will n...

Page 45: ...will show 3 functions at a time Floor operation time max 8 00 Maximum time for floor operation in hours and minutes Tank heat up time max 1 00 Maximum time for heating the tank in hours and minutes Ta...

Page 46: ...ation ON OFF of the pump Flow rate XX X L min Max Duty 0x40 0xFE Pump ON OFF Air Purge 7 2 Pump down To set the pump down operation Pump down operation ON 7 3 Dry concrete To dry the concrete floor wa...

Page 47: ...Select Single when one remote controller is connected Select Dual when two remote controllers are connected Second remote controller can be used for zone 2 room temperature control Single Selection o...

Page 48: ...e check Ensure that the water pressure is between 0 5 bar and 3 0 bar In case the water pressure is out of the above range consult an authorised dealer Water pressure can be checked through following...

Page 49: ...g up and venting until all air has been removed and the pressure is correct The climate system may require topping up after venting User In order to ensure optimal performance of the units user may in...

Page 50: ...er time to heat up System does not heat up instantly System will take some time to heat up the water if it starts to operate at cold water temperature Backup heater is automatically turned ON when it...

Page 51: ...8 High pressure protection H99 Indoor freeze prevention Error No Error explanation F12 Pressure switch activated F14 Poor compressor rotation F15 Fan motor lock error F16 Current protection F20 Compre...

Page 52: ...t phone device to prevent miss operation Do not use other remote control communication and operation device not specified by an authorised dealer or specialist Use under the agreement of Terms of Serv...

Page 53: ...ith an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel should be handl...

Page 54: ...Memo...

Page 55: ...Memo...

Page 56: ...untry Hotline Phone Number Country Hotline Phone Number Austria 0800 700666 Hungary 36 1 382 60 60 Baltic 46 8 680 26 50 Netherlands 31 0 736402538 Bulgaria 359 2 971 29 69 Norway 47 210 339 99 Croati...

Reviews: