33
Product description
Technical data and limitations – PACi systems
AHU Kit
PAW-280PAH2(L)
Outdoor unit
PACi Standard
1-phase
U-60PEY1E5
U-71PEY1E5
U-100PEY1E5 U-125PEY1E5
Nominal cooling capacity
kW
6.0
7.1
10.0
12.5
Nominal heating capacity
kW
7.0
8.0
11.2
14.0
Air volume (Cooling)
Min (factory)
m³/h
540
540
840
1,140
Max (factory)
m³/h
960
960
1,980
2,100
Air volume (Cooling),
subject to restrictions¹
Max
m³/h
1,450
1,600
2,400
2,500
AHU DX coil heat
exchanger volume
Min (factory)
dm
3
1.3
1.3
1.5
1.5
Max (factory)
dm
3
1.4
1.4
1.9
1.9
AHU DX coil heat
exchanger volume,
subject to restrictions
2
Max
dm
3
1.8
2.0
2.8
2.75
Additional ref. charge kg/dm
3
0.9
0.9
0.9
0.9
Max. additional
refrigerant charge
kg
0.36
0.54
0.81
0.76
Max. pipe length
m
40
35
30
30
Max. ambient temp.
for pump down
°C
n/a
n/a
35
25
Heat exchanger front
area
Min
m
2
–
–
0.43
0.43
Max
m
2
–
–
0.51
0.51
Power source
V / ph / Hz 230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Dimensions (enclosure) H x W x D
mm
278 x 278 x 180 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180
Net weight
Advanced / Light
kg
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
Protection class
IP65
IP65
IP65
IP65
Piping length
Min / Max
m
3 / 40
3 / 35
5 / 30
5 / 30
Precharged length
Max
m
20
20
15
15
Additional refrigerant charge
g/m
40
40
50
50
Piping connections
Liquid pipe
Inch (mm) 3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
Intake temperature of
AHU Kit
1
Cooling (Min / Max)
°C
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
(13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB)
Heating (Min / Max) °C
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max)
°C
-10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C
-20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
AHU Kit
PAW-280PAH2(L)
Outdoor unit
PACi Standard
3-phase
U-100PEY1E8 U-125PEY1E8 U-140PEY1E8
Nominal cooling capacity
kW
10.0
12.5
14.0
Nominal heating capacity
kW
11.2
14.0
16.0
Air volume (Cooling)
Min (factory)
m³/h
840
1,140
1,140
Max (factory)
m³/h
1,980
2,100
2,160
Air volume (Cooling),
subject to restrictions¹
Max
m³/h
2,400
2,500
2,600
AHU DX coil heat
exchanger volume
Min (factory)
dm
3
1.5
1.5
1.5
Max (factory)
dm
3
1.9
1.9
1.9
AHU DX coil heat
exchanger volume,
subject to restrictions
2
Max
dm
3
2.8
2.75
2.8
Additional ref. charge kg/dm
3
0.9
0.9
0.9
Max. additional
refrigerant charge
kg
0.81
0.76
0.81
Max. pipe length
m
30
30
30
Max. ambient temp.
for pump down
°C
35
25
n/a
Heat exchanger front
area
Min
m
2
0.43
0.43
0.43
Max
m
2
0.51
0.51
0.51
Power source
V / ph / Hz 230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Dimensions (enclosure) H x W x D
mm
278 x 278 x 180 278 x 278 x 180 278 x 278 x 180
Net weight
Advanced / Light
kg
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
Protection class
IP65
IP65
IP65
Piping length
Min / Max
m
5 / 30
5 / 30
5 / 30
Precharged length
Max
m
15
15
15
Additional refrigerant charge
g/m
50
50
50
Piping connections
Liquid pipe
Inch (mm) 3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
Intake temperature of
AHU Kit
1
Cooling (Min / Max)
°C
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
(13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB)
Heating (Min / Max) °C
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max)
°C
-10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C
-20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
To be continued on next page.