43
Installation
● The thermistor wire must point downwards from the thermistor to avoid water
reaching the thermistor.
● The thermistor wire must be inserted drooped in the AHU body with the droop-
ing wire being close to the AHU Kit.
Inside of AHU
AHU Kit
Drooping wire
Important
If there are multiple heat exchangers in one
ECOi system
, an individual thermistor must be
installed for each heat exchanger.
4.4.1 Installation of thermistor on gas pipe
Installation of thermistor on gas pipe – ECOi and ECO G systems
Mount “E3” thermistor to gas pipe of AHU heat exchanger according to the following
instructions.
For PAW-160MAH2(L)
1. Attach the gas pipe thermistor onto the collecting gas pipe in the heat exchanger.
i