49
Electrical Wiring
5 Electrical Wiring
5.1 General precautions on wiring
WARNING
Electric shock from live power supply cords
Electric shock may result from contact with live power supply cords.
► Wiring installation must only be performed by a qualified electrician.
► Before starting to work on any machines or devices, always switch off the power
supply and lock it in switched-off position.
CAUTION
The following precautions need to be followed strictly in the context of working on any
electrical wiring, in order to avoid hazardous situations, which
could result in minor or
moderate injury.
► Before wiring, confirm the rated voltage of the unit as shown on its nameplate,
then carry out the wiring closely following the wiring diagram.
► This equipment is not provided with a power supply cord. Circuit breaker must
be incorporated in the fixed wiring in accordance with national wiring regula-
tions. The circuit breaker must be approved, suitable for the voltage and current
ratings of equipment and have a contact separation in all poles.
► To prevent possible hazards from insulation failure, the unit must be grounded.
► Each wiring connection must be done in accordance with the wiring system
diagram. Wrong wiring may cause the unit to misoperate or become damaged.
► Do not allow wiring to touch the refrigerant tubing, compressor, or any moving
parts of the fan.
► Unauthorized changes in the internal wiring can be very dangerous. The manu-
facturer will accept no responsibility for any damage or misoperation that occurs
as a result of such unauthorized changes.
► Regulations on wire diameters differ from locality to locality. For field wiring
rules, please refer to the relevant local electrical codes before beginning.
You must ensure that installation complies with all relevant rules and
regulations.
► To prevent malfunction of the air conditioner caused by electrical noise, care
must be taken when wiring as follows:
● The remote control wiring and the inter-unit control wiring should be wired
apart from the inter-unit power wiring.
● Use shielded wires for inter-unit control wiring (between units) and ground
the shield on both sides.
► If the power supply cord of this appliance is damaged, it must be replaced by a
repair shop designated by the manufacturer, because special-purpose tools are
required.