If measured values are output with a slight change in values depending on the
tab while the tab section is measured
1. Increase the TB.CNT value. (Be careful that the response time changes.)
2. Decrease the TB.THRES value. (Note that if it is set to an excessively small value, the tab
cancellation may be applied due to meandering of the sheet.)
■
If the measured value is held at the tab height
1. If the hold cannot be released, reset the measured value using an external input. In the
default setting, the purple external input 2 is used to reset the measured value.
2. Increase the TB.CNT value. (Be careful that the response time changes.)
3. Decrease the TB.THRS value. (Note that if it is set to an excessively small value, the tab
cancellation may be applied due to meandering of the sheet.)
7.7 Tab Cancellation Function
7-76
WUME-HGT-6
Summary of Contents for HG-T Series
Page 2: ... MEMO 2 WUME HGT 6 ...
Page 28: ... MEMO 2 8 WUME HGT 6 ...
Page 96: ... MEMO 5 50 WUME HGT 6 ...
Page 99: ... Note 2 Displayed only during calculation 6 1 Flow of Measurement Data WUME HGT 6 6 3 ...
Page 128: ... MEMO 6 32 WUME HGT 6 ...
Page 158: ... No timer OFF 7 2 Advanced Settings 7 30 WUME HGT 6 ...
Page 177: ...Example Positioning a glass plate Setting method 7 2 Advanced Settings WUME HGT 6 7 49 ...
Page 218: ...8 2 3 Side View Attachment HG TSV10 Units mm 8 2 Dimension Drawings 8 14 WUME HGT 6 ...
Page 221: ...10 Troubleshooting 10 1 Troubleshooting 10 2 10 2 Error Messages 10 5 WUME HGT 6 10 1 ...
Page 229: ...Menu Structure General Function Display WUME HGT 6 App 3 ...
Page 231: ...Menu Structure Extended Function Display WUME HGT 6 App 5 ...
Page 232: ... MEMO App 6 WUME HGT 6 ...
Page 235: ... MEMO WUME HGT 6 ...
Page 236: ...Panasonic Industrial Devices SUNX Co Ltd 2020 PRINTED IN JAPAN WUME HGT 6 ...