Specifications
6-10
6.2.4 Interface Specifications
Interface (COM port) for connecting PLC/External devices
Item
Specifications
RS232C type
RS422 / RS485 type
Communication standard
Conforms to RS-232C
(Non-isolated)
Conforms to RS422
(Non insulation type)
Communication
condition with
external
devices
Baud rate (bit/s)
9,600
、
19,200
、
38,400
、
57,600
、
115,200
Data length (bit)
7,8
Parity
None, Odd, Even
Stop bit (bit)
1
Transmission distance
(Total length)
Ma. 15 m
(Baud rate: 19,200 bit/s)
Ma. 500 m
(Baud rate: 115,200 bit/s)
Terminal resistance value
-
120Ω
Protocol
Protocol for Panasonic FP series PLC (MEWTOCOL)
Protocol for Panasonic FP7 series PLC (MEWTOCOL7)
General-purpose serial (Panasonic dedicated protocol)
Modbus RTU mode protocol (Master/Slave)
Other companies' PLC protocols
For the details, refer to the latest GTWIN HELP.
Connector
Connector terminal block (8-pin) (Note 1) (Note 2) (Note 3)
(Note 1): The (+) and (-) terminals are the power supply terminals for driving the main unit.
(Note 2): Regarding power supply voltage, please pay due consideration to the cable length so that the applied
voltage is within the operation voltage range.
(Note 3): When tightening the terminal block requires a flat-blade screwdriver with a blade size of 0.4 x 2.5 or special
screwdriver (part No.: AFP0806). The tightening torque should be 0.22 to 0.3 Nm.
Dedicated
wire
Size
Nominal cross-sectional
area
AWG#28 to 16
0.08 to 1.25 mm
2
* Use a wire of which temperature rating is 75 degrees or more.
Interface for transferring screen data (USB port)
Item
Specifications
Communication standard
USB2.0
Connector shape (Note 1)
USB MiniB type 5pin
Transmission distance
Max. 5 m
No. of connected units with PC
1 unit
(Note 1): Take care of handling of the connector not to add an excessive static electricity on the metal part
Summary of Contents for GT703
Page 10: ...Before You Start viii ...
Page 11: ...1 System Configuration ...
Page 15: ...2 Names and Functions of Parts ...
Page 25: ...3 Installation and Wiring ...
Page 40: ...Installation and Wiring 3 16 ...
Page 41: ...4 Connection with PLC ...
Page 76: ...Connection with PLC 4 36 ...
Page 77: ...5 Troubleshooting ...
Page 89: ...6 Specifications ...
Page 103: ...Record of changes Manual No Date Record of Changes WUME GT703H 01 Jul 2017 1st Edition ...
Page 104: ......