5.1
What to Do If an Error Occurs
5-5
Operation security function
Message
Cause
Solution
“Incorrect password.” Is displayed
on the login screen.
An unregistered
password was entered.
Enter the registered password.
“Incorrect password.” Is displayed
on the password change screen.
An incorrect password
was entered in the
Current password field.
Enter the registered password correctly.
”Please verify your password
again.” is displayed on the
password change screen.
The entered New
password and Confirm
password are different.
Enter the same password in the New
password and Confirm password fields.
”Use another password.” is
displayed on the password change
screen.
The password that has
been already registered is
tried to be registered.
Enter an unregistered new password.
”Password setting incomplete.” is
displayed on the password change
screen.
There are items that are
not entered.
Enter all items.
”Your password cannot be deleted.”
is displayed on the password
management screen.
Your password was tried
to be deleted.
Your password cannot be deleted.
If you want to delete it, select “System
Setting” > “Operation Security Password”
from the GTWIN menu and change the
setting content.
”Your level cannot be changed.” is
displayed on the password
management screen.
Your level was tried to be
changed.
Your security level cannot be changed.
If you want to change it, select “System
Setting” > “Operation Security Password”
from the GTWIN menu and change the
setting content.
Summary of Contents for GT703
Page 10: ...Before You Start viii ...
Page 11: ...1 System Configuration ...
Page 15: ...2 Names and Functions of Parts ...
Page 25: ...3 Installation and Wiring ...
Page 40: ...Installation and Wiring 3 16 ...
Page 41: ...4 Connection with PLC ...
Page 76: ...Connection with PLC 4 36 ...
Page 77: ...5 Troubleshooting ...
Page 89: ...6 Specifications ...
Page 103: ...Record of changes Manual No Date Record of Changes WUME GT703H 01 Jul 2017 1st Edition ...
Page 104: ......