3.2
Wiring the Power Supply
3-7
3.2.3 Wiring the COM Port
Accessory communication connector/applicable wiring
The communication connector used for the COM port (provided as an accessory with the
main unit) has a screw-tightening type of terminal block. Use the following items for wiring.
Suitable wires (strand wire)
Size
Cross-sectional area
AWG28 to 16
0.08 to 1.25mm
2
Use a special tool to tighten the terminal block of the communication connector.
Use a screwdriver made by us. (Product number: AFP0806) The tightening torque should be
0.22 to 0.3 Nm.
When doing RS485 communication using RS422 type
Please use the following cables or equivalent.
Suitable wires (strand wire)
Classification Cross-sectional view
Conductor
Insulator
Cable
diam.
Sample
appropriate cable
Size
Resistance
(at 20
°
C)
Material Thick-
ness
Shielded
twisted pair
1.25 mm
2
(
AWG16
)
or more
Max.
16.8
Ω/km
Poly-
ethylene
Max.
0.5mm
Approx.
8.5 mm
Hitachi Cable, Ltd.
KPEV-S1.25mm
2
×
1P
Belden 9860
0.5 mm
2
(AWG20)
or more
Max.
33.4
Ω/km
Poly-
ethylene
Max.
0.5mm
Approx.
7.8mm
Hitachi Cable, Ltd.
KPEV-S0.5mm
2
×
1P
Belden 9207
•
Use shielded twisted pair cables.
•
Use only one type of transmission cable. Do not mix more than 1 type.
•
When using shielded cable with crossover wiring for the RS485
transmission line, grounded one end.
Summary of Contents for GT703
Page 10: ...Before You Start viii ...
Page 11: ...1 System Configuration ...
Page 15: ...2 Names and Functions of Parts ...
Page 25: ...3 Installation and Wiring ...
Page 40: ...Installation and Wiring 3 16 ...
Page 41: ...4 Connection with PLC ...
Page 76: ...Connection with PLC 4 36 ...
Page 77: ...5 Troubleshooting ...
Page 89: ...6 Specifications ...
Page 103: ...Record of changes Manual No Date Record of Changes WUME GT703H 01 Jul 2017 1st Edition ...
Page 104: ......