15.5.17 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
To maintain DC voltage level supply to power transistor.
To detect high DC voltage level after rectification.
Malfunction Caused
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level.
When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF
relay RY-C.
Troubleshooting
Summary of Contents for CS-E9PD3EA
Page 24: ...24 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 25: ...25 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E9PD3EA ...
Page 26: ...26 5 1 2 CS E12PD3EA ...
Page 27: ...27 5 2 Outdoor Unit 5 2 1 CU E9PD3EA 5 2 2 CU E12PD3EA ...
Page 28: ...28 6 Refrigeration Cycle Diagram ...
Page 29: ...29 7 Block Diagram 7 1 CS E9PD3EA CU E9PD3EA ...
Page 30: ...30 7 2 CS E12PD3EA CU E12PD3EA ...
Page 31: ...31 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 CU E9PD3EA ...
Page 36: ...36 9 2 2 CU E12PD3EA ...
Page 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU E9PD3EA ...
Page 39: ...39 10 2 1 2 CU E12PD3EA ...
Page 47: ...47 11 1 6 1 WIRE STRIPPING AND CONNECTING REQUIREMENT ...
Page 62: ...62 14 1 2 CU E12PD3EA ...
Page 66: ...66 15 4 Error Codes Table ...