In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of compressor or fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
Normal pressure and outlet air temperature(standard)
Cooling mode
Gas side pressure
Mpa
(kg/cm G)
2
0.4~0.6(4~6)
12~16
Outlet air
tempera ture
( )
℃
★
Condition: indoor fan speed: high
outdoor temperature: 35
(cooling mode)
℃
Difference in the
intake and outlet
air temperature
More than 8
(15 minutes aften an
operation is started) at the cooling mode
℃
Normal
Measuring the air
temperature difference
Measuring electric current
during operation
Measuring gas side
pressure
Less than 8
at the cooling mode.
℃
Value of electric
current
during operation
Higher than
specified
Dusty heat exchanger
preventing heat radiation
Excessive am ount
of refrigerant
Lower than specified
Gas side pressure
Cooling
mode
High
Low
Low
Inefficient compressor
Insufficient refrigerant
clogged strainer or
capillary tube
13.1. Refrigeration cycle system
13 Troubleshooting Guide
CS-C45FFH / CU-C45FFH
Air outlet vent
Thermometer
Air inlet vent
Summary of Contents for CS-C45FFH
Page 8: ...8 4 Dimensions Indoor Unit CS C45FFH CU C45FFH 357 23 5X4 1880 16 5 56 Remote Controller ...
Page 9: ...9 Outdoor Unit CS C45FFH CU C45FFH CU C45FFH 900 620 140 40 5 320 ...
Page 43: ...CS C45FFH CS C45FFH CU C45FFH 43 44 37 38 39 40 41 42 14 13 43 ...
Page 45: ...17 Exploded View CS C45FFH CU C45FFH 45 ...
Page 46: ...CS C45FFH CU C45FFH 46 ...