8 Operation Details
8.1.
Cooling Mode Operation
When selecting the Cooling Mode Operation, the unit will operate according to the setting by the Remote Controller or
the control panel on the indoor unit and the operation is as the following.
CS-C45FFH / CU-C45FFH
Time Delay Safety Control
3 min.----If the compressor stops, it will not restart within 3 minutes.(Protection of compressor).
7 Minutes Time Save Control
7 min.----The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
Evaporator
Temperature
( )
℃
10
2
Restart
4 minutes
Compressor ceases
Time
Anti-Freezing Control
If temperature of evaporator is lower than 2
continuously
for 4 minutes, the compressor will cease to prevent the
evaporator from freezing. Fan speed setting will not be
changed.
When temperature of evaporator reaches 10 ,compressor
will restart in 3 minutes.
During Cooling Mode Operation, the Time Delay Safety
Control is available.
℃
℃
※
If th e temperature of outdoor heat exchanger is belo w 12 , a ten-minutes timer will sta rt timing . When the
situation persists for 10 minutes, the compressor will stop and time delay safety control is ava ilable. When
the temperature of outdoor heat exchanger rises to 13 .5
or a bove, the timer can be reset.
℃
℃
When the compressor is started, within 30 seconds ,
the outdoor fan speed is controlled by the temperature
of outdoor heat exchanger. (Refer to Outdoor Fan Motor
Control)
The fan speed changes every two minutes and it is determined
by the tem perature of 1
’
50
’’
and 2
’
after the previous
determination.
If te mperature of outdoor heat exchanger is 45
or ab ove
the timer will be cleared. If the temperature declines below
45 , the tim er starts to operate.
℃
℃
Outdoor Temperature Control
Outdoor Fan Start Control
Outdoor Fan Low Temp Control
Temperatu re
of Condense r
T<0
0
T<10
10
T<20
20
T<25
25
T
℃
℃≤
℃
℃ ≤
℃
℃ ≤
℃
℃≤
Fan Speed (Tap)
1
4
7
17
30
Temp of
Exchanger
50
℃
40
℃
35
℃
30
℃
25
℃
NO 30
Fan 2 taps up
Fan 1 tap up
Fan 1 tap down
Present situation remains
Compre sso r Rever se R otation Pro tection Control
Compressor runs continuesely for 9 minutes or more.
If the compr essor is operatin g co ntinuously for 5 minutes or longer and temperature difference between intake
air and indoor heat exchanger is 2.5
°
C or less for 2 mi nutes, compress or w ill stop a nd restart automatically.
(Time delay safety control is valid)
Compressor starts for 5 minutes
T
2.5
for 2 minutes
▲
≤
°
C
Compressor
OFF
Compressor restarts
▲
T = I
Indoor heat exchager temperature
This is to protect reverse rotation of the compressor whten there is a instantaneous power failure.
ntake air temperature -
Summary of Contents for CS-C45FFH
Page 8: ...8 4 Dimensions Indoor Unit CS C45FFH CU C45FFH 357 23 5X4 1880 16 5 56 Remote Controller ...
Page 9: ...9 Outdoor Unit CS C45FFH CU C45FFH CU C45FFH 900 620 140 40 5 320 ...
Page 43: ...CS C45FFH CS C45FFH CU C45FFH 43 44 37 38 39 40 41 42 14 13 43 ...
Page 45: ...17 Exploded View CS C45FFH CU C45FFH 45 ...
Page 46: ...CS C45FFH CU C45FFH 46 ...