(Indoor un it)
(L iq uid sid e)
(Ou tdo or unit)
(Gas side)
3-way
valve
Ope n
Low
High
Ope n
Op en
Vacuum pump
3-way
valve
O pe n
(No refrigerant in the refrigeration cycle)
11.5. Evacuation
Procedure
1.
Connect the vacuum pump to the charge set
’
s centre hose.
Turn on the vacuum pump to evacuate the unit.
Close the valve (Low side and High side) on the charge set,
turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after the
vacuum pump is turned off).
Disconnect the charge hose from the vacuum pump.
2.
Confirm that the gauge needle has moved toward -76
cmHg (-0.1MPa).
Apply the vacuum for approximaterly 1 hour (vacuum of
4 mmHg or less).
3.
4.
●
●
35
CS-C45FFH / CU-C45FFH