Regumaq X-80 Potable water circulation set
Commissioning
5.4 Electrical connection of the high-
efficiency pump
For details on connecting the high-efficiency
pump, consult the instructions for the product
you have selected.
The power supply may only be established by a
qualified electrician.
WARNING
Death or serious bodily injury due to electric
shock!
Since the fresh water station is supplied with
voltage via an earthing contact plug, N and L can be
interchanged by the position of the plug in the
socket. It is therefore not ensured that the power
supply for the high-efficiency pump from the
controller always has the same polarity. In
particular, it is possible that voltage (L) is applied to
the neutral conductor (N) marked in blue.
!
Establish a fixed cable connection between the
high-efficiency pump and the controller!
NOTICE
Overload and damage to the controller!
If a high-efficiency pump is connected to the
controller whose rated current exceeds the
controller's load limit (1 A) during operation, the
controller may be damaged. (Example: Wilo-Stratos
PARA Z 25/1-12 RK 180)
!
Use the Oventrop installation relay (item no.
1152089) between the controller and the high-
efficiency pump.
6. Commissioning
6.1 Configuration of the circulation
function
f
Configure the circulation function according to the
specifications in the operating instructions for your
fresh water station.
6.2 Filling of the circulation pipe
1
Open the ball valve (position
8
2
Proceed as described in the instructions for filling the
potable water circuit in the operating instructions for
your fresh water station.
3
Check all components and screw connections for
leaks.
4
Tighten any screw connections that are too loose.
5
Establish the power supply of the fresh water station.
6
Close the fresh water station with the upper shell.
Z
The fresh water station is ready for operation.