Regumaq X-80 Potable water circulation set 

Commissioning

5.4  Electrical connection of the high-

efficiency pump

For details on connecting the high-efficiency 

pump, consult the instructions for the product 

you have selected.

The power supply may only be established by a 

qualified electrician.

WARNING

Death or serious bodily injury due to electric 

shock!

Since the fresh water station is supplied with 

voltage via an earthing contact plug, N and L can be 

interchanged by the position of the plug in the 

socket. It is therefore not ensured that the power 

supply for the high-efficiency pump from the 

controller always has the same polarity. In 

particular, it is possible that voltage (L) is applied to 

the neutral conductor (N) marked in blue.

 

!

Establish a fixed cable connection between the 

high-efficiency pump and the controller!

NOTICE

Overload and damage to the controller!

If a high-efficiency pump is connected to the 

controller whose rated current exceeds the 

controller's load limit (1 A) during operation, the 

controller may be damaged. (Example: Wilo-Stratos 

PARA Z 25/1-12 RK 180)

 

!

Use the Oventrop installation relay (item no. 

1152089) between the controller and the high-

efficiency pump.

6.  Commissioning

6.1  Configuration of the circulation 

function

 

f

Configure the circulation function according to the 

specifications in the operating instructions for your 

fresh water station.

6.2  Filling of the circulation pipe

Open the ball valve (position 

8

 in Fig. 2 on page 5).

Proceed as described in the instructions for filling the 

potable water circuit in the operating instructions for 

your fresh water station.

Check all components and screw connections for 

leaks.

Tighten any screw connections that are too loose.

Establish the power supply of the fresh water station.

Close the fresh water station with the upper shell.

 

Z

The fresh water station is ready for operation.

8

138159084-V02.03.2022

Summary of Contents for Regumaq X-80

Page 1: ...Regumaq X 80 Potable water circulation set Operating instructions EN ...

Page 2: ...structions 4 3 Technical description 5 3 1 Design 5 3 2 Functional description 5 3 3 System examples 5 3 3 1 Pump and ball valve in close proximity to the fresh water station 5 3 3 2 Alternative placement of the high efficiency pump and ball valve 6 3 4 Technical data 6 3 5 Dimensions of the pipe elbow 6 4 Transport and storage 7 5 Installation 7 5 1 Required tools 7 5 2 Mounting of the pipe elbow...

Page 3: ...tional safety is only guaranteed if the product is used as intended The Regumaq X 80 potable water circulation set is used to connect circulation pipes for the supply of hot potable water to the Oventrop Regumaq X 80 fresh water stations Any use beyond and or different from this is considered unintended use Claims of any kind against the manufacturer and or his authorised representatives for damag...

Page 4: ...low the product to cool down before working on it Wear suitable protective clothing to avoid unprotected contact with hot fittings and plant components 2 3 4 Risk of injury due to the weight of the product Always wear safety shoes during installation 2 3 5 Risk of injury from improper work Stored energy angular components points and corners can cause injuries Ensure there is sufficient space befor...

Page 5: ...ter station to the draw off point and a parallel pipe leads back The high efficiency pump available separately moves the hot potable water in the circulation circuit This means that hot water of the desired temperature is always available at the draw off points 3 3 System examples 3 3 1 Pump and ball valve in close proximity to the fresh water station 1 9 11 10 13 12 2 3 4 5 6 8 7 Fig 2 System exa...

Page 6: ...iciency pump 4 Piping 5 Ball valve 3 4 Technical data General information Operating pressure ps Max 10 bar Operating temperature ts Max 95 C Connections Circulation G 1 external thread flat sealing Potable water circuit Fluid Potable water Material Pipe group Brass dezincification re sistant brass Check valve Plastic Ball valve Bronze Seals Fibre material EPDM Thermal insulation Expanded polypropy...

Page 7: ... Slowly close the shutoff ball valve in the hot potable water return position 13 in Fig 2 on page 5 4 Unscrew the cap of the fill and drain ball valve for hot potable water position 12 in Fig 2 on page 5 and connect a drain hose 5 Drain the potable water circuit of the fresh water station 6 Unscrew the cap from the connection for the circulation set position 3 in Fig 2 on page 5 7 Mount the check ...

Page 8: ...mage to the controller If a high efficiency pump is connected to the controller whose rated current exceeds the controller s load limit 1 A during operation the controller may be damaged Example Wilo Stratos PARA Z 25 1 12 RK 180 Use the Oventrop installation relay item no 1152089 between the controller and the high efficiency pump 6 Commissioning 6 1 Configuration of the circulation function f Co...

Page 9: ...eck valve is intact close the lateral connection of the ball valve position 1 in Fig 6 on page 9 8 Open the ball valve slowly by turning the rotary handle position 2 in Fig 6 on page 9 by 90 Z The functional check of the check valve is complete 8 Troubleshooting MALFUNCTION CAUSE REMEDY The high effi ciency pump does not run The power sup ply is interrupt ed Check the pow er supply The high effi c...

Page 10: ...138159084 V02 03 2022 Oventrop GmbH Co KG Paul Oventrop Str 1 59939 Olsberg Tel 49 2962 820 Fax 49 2962 82400 mail oventrop com www oventrop com ...

Reviews: