„Aktor M ST L Modbus“ 

Technical description

9

101274584-V01.11.2019

3.3  Technical data

Technical data
Operating voltage

24 V AC ±10 %, 50/60 Hz; 
4.8 VA; 24 V DC ±10 %; 2.5 

W

Power consumption

Dimensioning: 

 

-

9.0 VA (24 V AC)

 

-

4.7 W (24 V DC)

nominal: 

 

-

4.8 VA (24 V AC)

 

-

2.5 W (24 V DC)

Start up load

 

-

24 V DC; 5.0 A; 0.025 A

2

s

 

-

24 V AC; 7.2 A; 0.052 A

2

s

Interface

RS485 Modbus RTU slave; 

max. 1000 m depending 
on the baud rate

Drive

Directly via Modbus via au

-

tomation station or gateway

Inputs and outputs

2 universal in- or outputs 

(P1, P2) independently para

-

metrizable via Modbus as:

 

-

binary input, volt free 
max. 500 Ohm; 1 mA; 13 

V DC

 

-

analogue input, see table 
"sensor types", S.4

 

- analogue output 0..10 V 

DC only P2

Connection

Two pre-assembled cables

1.5 m; 2 x 2 x 0.5 mm

2

 

shielded  

and 1.5 m; 4 x 0.5 mm

2

Display

LED display for operating 
voltage and status

Motor deactivation

Drive stem: 

 

extending = load-depend-

ent, 

 

retracting = load-dependent

Travel noise

<31 dB (A)

Piston stroke

max. 14 mm

Floating time

22 s/mm

Operating power

nominal 500 N

Position indicator

Stroke scale

Valve anti-blocking 

function

Optional activation  

Parametrization via Modbus

Permissible fluid 

temperature in the 

valve

0 -120 °C

Ambient tempera-

ture

0 - 50 °C

Ambient humidity

In operation: 0 - 85 % r.h., 

not condensing

Out of operation: 0 - 85 r.h., 

not condensing

Overvoltage cate-

gory

Degree of protection

Pollution degree

2

Protection class

IP54 

NOTICE

Short circuit due to drip-

ping water

 

f

Do not feed the cable in 
from the top.

Protective system

III according to EN 60730

Installation position

360° 

Maintenance

maintenance-free

Weight

396 g

Bus communication
Interface

EIA-485 / RS-485

Type of transmission

Modbus RTU slave

Supported baud 

rates

9.600, 19.200, 38.400 
(factory setting), 57.600, 

115.200 bps

Start/stop bits

8N1, 8N2 (factory setting)

Number of bus par-

ticipants

Up to 32 recommended, 

max. 64

Bus load

1/8 unit load

Termination

Switchable in the appliance, 

120 Ohm

Bias network

To be set in the master

Recommended line

Twisted pair cable with 

shield (characteristic imped-
ance

about 120 Ohm)

Bus topology with 

115.200 baud

Recommended max. line 
length 500 m

Bus topology with 

38.400 / 57.600 baud

Recommended max. line 
length 750 m

Bus topology with 

9.600/19.200 baud

Recommended max. line 
length 1000 m

Stub lines

Max. line length 2 m

Supported Modbus 

function codes

Code Function
0x03

Read holding reg-
ister

0x06

Write holding reg-
ister

0x03

Read holding mul-
tiple

0x10

Write holding mul-
tiple

Summary of Contents for Aktor M ST L Modbus

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L Modbus 24 V DN 40 50...

Page 2: ......

Page 3: ...3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Basic functions 7 3 2 2 Calculation functions 8 3 2 3 Limitation function...

Page 4: ...1 2019 6 3 2 Via the Modbus parametrization 13 6 4 Manual operation 13 6 4 1 Extending the drive stem 13 6 4 2 Retracting the drive stem 14 7 Maintenance 14 8 Removal 14 9 Disposal 14 10 Appendix 15 1...

Page 5: ...le connec tions 1 3 Extent of supply Electromotive actuator Aktor M ST L Modbus 24 V Operating instructions 1 4 Contact Address OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY Technic...

Page 6: ...s injury if not avoided CAUTION Indicates a possible danger with lower risk The situation may lead to minor and revers ible injury if not avoided NOTICE Indicates a situation that may lead to damage t...

Page 7: ...e actuator is operated with steady control The control signal 0 100 is transmitted via Modbus communication The current position 0 100 can be queried via Modbus Valve anti blocking function The actuat...

Page 8: ...d via Modbus and the calculated current output When exceeded the volume flow will be reduced until the limit value is reached again 3 2 4 Control function Output control registers 130 200 301 310 311...

Page 9: ...s Permissible fluid temperature in the valve 0 120 C Ambient tempera ture 0 50 C Ambient humidity In operation 0 85 r h not condensing Out of operation 0 85 r h not condensing Overvoltage cate gory De...

Page 10: ...ches Bit 1 bis 6 are set to OFF see section 5 3 1 on page 12 5 1 Fitting of the actuator Make sure that there is enough space for the installation of the actuator The actuator must only be connected t...

Page 11: ...e to dripping water f Do not feed the cable in from the top 1 Remove the casing cover 2 Connect the data lines for the Modbus and if required the lines for the universal inputs according to the assign...

Page 12: ...D is located under the casing cover above the terminal on the right hand side and dis plays the operating status of the actuator The status LED is visible even when the cover is closed Status LED Mean...

Page 13: ...error message will be gen erated again immediately 5 Baud rate change The currently set parameters of the register addresses 105 107 are applied 6 4 Manual operation The manual mode is only intended...

Page 14: ...Disconnect all electrical connections 4 Press the push button to release the latched valve stem position 1 in Illust 2 on page 7 5 Unscrew the collar nut 6 Remove the actuator from the valve Also remo...

Page 15: ...1 23 2 uint16 HW identifier r e g 0x00F1 3 uint16 SerNum1 r 0 65535 4 uint16 SerNum2 r 0 65535 5 uint16 SerNum3 r 0 65535 101 uint16 Time hour r w 0 23 to be set manually no battery buffered RTC 102...

Page 16: ...input 3 KP10 4 NI1000_DIN 5 NI1000_LG 6 PT1000 8 Y output 0 10V register 426 9 Y feedback 0 10V register 401 10 Change over output 0V cooling 5V shut off 10V heating 127 uint16 Inversion P2 input r w...

Page 17: ...ure control according to register differential temperature 201 uint16 Change over mode r w 0 Shut off 1 Heating 2 Cooling 3 Automatic according to flow temperature 300 uint16 Nominal value room temper...

Page 18: ...w Current flow temperature in C 10 write protected in case of assigned source P1 or P2 405 int16 Return temperature r w Current return temperature in C 10 write protected in case of assigned source P...

Page 19: ......

Page 20: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101274584 V01 11 2019...

Reviews: