„Aktor M ST L Modbus“ Operation

13

101274584-V01.11.2019

6.3  Initialisation run

6.3.1  By address change

The actuator will perform an initialisation run if the 
Modbus address is changed (see section 

5.3.2 on 

page 12

). 

6.3.2  Via the Modbus parametrization

Register 

address

Name R/W Values

138

Com-
mand

r/w

0: Normal operation

1: Valve adaptation/initiali

-

sation run

2: Test run: manual flush

-

ing function (once), after 
that the valve will again 

be controlled according to 
the set operating mode

3: Sync: manual flushing 
function (once), after that 
the valve will again be 

controlled according to 
the set operating mode

4: Error reset: Each incom

-

ing error will generate an 

error message in register 
318. The error message 

can be reset with the help 

of the

Error Reset. In case of 
permanent errors, the 
error message will be gen

-

erated again immediately.

5: Baud rate change. The 

currently set parameters 
of the register addresses 
105...107 are applied.

6.4  Manual operation

The manual mode is only intended for mounting and 
test purposes.

In manual mode, the stem can be extended and 
retracted manually with the help of a magnet.

CAUTION

Risk of scalding due to hot fluids

In manual mode the actuator might not close 

fully. 
There is a risk of scalding due to the uninten-

tional discharge of hot water.

 

f

Only carry out work when the system is 

depressurised.

 

f

Allow the system to cool down.

 

f

Wear safety goggles.

1

Illust. 6:  Manual operation

(1)

Magnet

6.4.1  Extending the drive stem

1. 

Move the actuator into the mounting position (DIP 
switches (Bit 1 to 6) set to “OFF”).

 

Z

The drive stem will be retracted.

 

Z

The LED will flash green quickly.

2. 

Stroke along the right side of the actuator with the 
magnets (position (1) in Illust. 6 on page 13).

 

Z

The drive stem will be extended.

 

Z

The LED will flash yellow.

Summary of Contents for Aktor M ST L Modbus

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L Modbus 24 V DN 40 50...

Page 2: ......

Page 3: ...3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Basic functions 7 3 2 2 Calculation functions 8 3 2 3 Limitation function...

Page 4: ...1 2019 6 3 2 Via the Modbus parametrization 13 6 4 Manual operation 13 6 4 1 Extending the drive stem 13 6 4 2 Retracting the drive stem 14 7 Maintenance 14 8 Removal 14 9 Disposal 14 10 Appendix 15 1...

Page 5: ...le connec tions 1 3 Extent of supply Electromotive actuator Aktor M ST L Modbus 24 V Operating instructions 1 4 Contact Address OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY Technic...

Page 6: ...s injury if not avoided CAUTION Indicates a possible danger with lower risk The situation may lead to minor and revers ible injury if not avoided NOTICE Indicates a situation that may lead to damage t...

Page 7: ...e actuator is operated with steady control The control signal 0 100 is transmitted via Modbus communication The current position 0 100 can be queried via Modbus Valve anti blocking function The actuat...

Page 8: ...d via Modbus and the calculated current output When exceeded the volume flow will be reduced until the limit value is reached again 3 2 4 Control function Output control registers 130 200 301 310 311...

Page 9: ...s Permissible fluid temperature in the valve 0 120 C Ambient tempera ture 0 50 C Ambient humidity In operation 0 85 r h not condensing Out of operation 0 85 r h not condensing Overvoltage cate gory De...

Page 10: ...ches Bit 1 bis 6 are set to OFF see section 5 3 1 on page 12 5 1 Fitting of the actuator Make sure that there is enough space for the installation of the actuator The actuator must only be connected t...

Page 11: ...e to dripping water f Do not feed the cable in from the top 1 Remove the casing cover 2 Connect the data lines for the Modbus and if required the lines for the universal inputs according to the assign...

Page 12: ...D is located under the casing cover above the terminal on the right hand side and dis plays the operating status of the actuator The status LED is visible even when the cover is closed Status LED Mean...

Page 13: ...error message will be gen erated again immediately 5 Baud rate change The currently set parameters of the register addresses 105 107 are applied 6 4 Manual operation The manual mode is only intended...

Page 14: ...Disconnect all electrical connections 4 Press the push button to release the latched valve stem position 1 in Illust 2 on page 7 5 Unscrew the collar nut 6 Remove the actuator from the valve Also remo...

Page 15: ...1 23 2 uint16 HW identifier r e g 0x00F1 3 uint16 SerNum1 r 0 65535 4 uint16 SerNum2 r 0 65535 5 uint16 SerNum3 r 0 65535 101 uint16 Time hour r w 0 23 to be set manually no battery buffered RTC 102...

Page 16: ...input 3 KP10 4 NI1000_DIN 5 NI1000_LG 6 PT1000 8 Y output 0 10V register 426 9 Y feedback 0 10V register 401 10 Change over output 0V cooling 5V shut off 10V heating 127 uint16 Inversion P2 input r w...

Page 17: ...ure control according to register differential temperature 201 uint16 Change over mode r w 0 Shut off 1 Heating 2 Cooling 3 Automatic according to flow temperature 300 uint16 Nominal value room temper...

Page 18: ...w Current flow temperature in C 10 write protected in case of assigned source P1 or P2 405 int16 Return temperature r w Current return temperature in C 10 write protected in case of assigned source P...

Page 19: ......

Page 20: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101274584 V01 11 2019...

Reviews: