„Aktor M ST L Modbus“ Appendix
15
101274584-V01.11.2019
10. Appendix
10.1 Modbus topology
24V
D
-
0
V
D
+
1 2 3 4
AKTOR
24V
D
-
0
V
D
+
1 2 3 4
AKTOR
24V
D
-
0
V
D
+
1 2 3 4
AKTOR
24V
D
-
0
V
D
+
MASTER
24V
24V
0V
02
01
n
00
Illust. 7: Modbus topology
NOTICE
Disturbances during signal transmission in the bus system
If the Modbus is not terminated correctly, communication disturbances between the components may
occur.
f
Install a terminal resistance (120 Ohm) at the beginning and the end of the Modbus between the
data lines D+ and D-.
10.2 Data point list
Register
address
Data
type
Name
R/W Values
0
uint16
Type
r
1
: Aktor
1
uint16
FW version
r
e.g. 123 = version 1.23
2
uint16
HW identifier
r
e.g. 0x00F1
3
uint16
SerNum1
r
0-65535
4
uint16
SerNum2
r
0-65535
5
uint16
SerNum3
r
0-65535
101
uint16
Time hour
r/w
0-23 to be set manually (no battery buffered RTC)
102
uint16
Time minute
r/w
0-59 to be set manually (no battery buffered RTC)
105
uint16
RS485 Baud rate
r/w
0: default (38400,N,8,2) ; 1: 9.600 ; 2: 19.200 ; 3: 38.400 ; 4:
57.600 ;
5: 115.200
106
uint16
RS485 Stop bits
r/w
1, 2
107
uint16
RS485 Parity
r/w
0: none ; 1: even ; 2: odd
110
uint16
Selection of the current
valve characteristic line
r/w
0: linear
1: Cocon QTR DN40 1500-7500 l/h
2: Cocon QTR DN50 IG 3500-14000 l/h
3: Cocon QTR DN40 AG 1500-7500 l/h
4: Cocon QTR DN50 AG 3500-10000 l/h
5: Cocon QFC DN40 1500-7500 l/h
6: Cocon QFC DN50 2000-8000 l/h
113
uint16
Maximum volume flow
of the selected valve
r
In l/h, is set when selecting the valve characteristic line