Technical description 

„Aktor M ST L Modbus“

8

101274584-V01.11.2019

The cycle time can be configured via the Modbus 
parametrization.
If the value is zero, this function is deactivated.

3.2.2  Calculation functions

Calculation of the volume flow

In combination with a pressure independent control 
valve “Cocon QTR/QFC”, the current volume flow is 

calculated on the basis of the set valve characteristic 
line and the current position of the actuator and can 

be queried via Modbus.

Calculation of the thermal output

The current thermal output is calculated on the basis 

of the calculated volume flow and the temperature 
difference between the supply and return pipe and 
can be queried via Modbus.

3.2.3  Limitation function

Return temperature limitation (register 315)

Return temperature limitation is carried out on the 

basis of the limit value configured via Modbus and 

the current measured return temperature. When ex-

ceeded or undercut, the volume flow will be reduced 

until the limit value is reached again.

Limitation of the thermal output (register 314)

Limitation of the thermal output is carried out on the 

basis of the limit value configured via Modbus and 
the calculated current output. When exceeded, the 
volume flow will be reduced until the limit value is 

reached again.

3.2.4  Control function

Output control (registers 130, 200, 301, 310, 311, 410)

Control to a defined output value can be carried out 

on the basis of the calculated current output.

Room temperature control (registers 131, 200, 300, 

310, 311, 403)

Room temperature control is carried out on the basis 

of the nominal temperature configured via Modbus 

and the transmitted current room temperature.

Return temperature control (registers 130, 200, 302, 

310, 311, 404, 405)

Return temperature control is carried out on the ba-

sis of the nominal temperature configured via Mod

-

bus and the current measured return temperature.

3.2.5  System monitoring

Leakage detection

A possible internal leakage is detected on the basis 

of the measured flow and return temperature with the 

valve closed.
A leakage is detected if the measured temperature 

difference exceeds 8 K for at least 6 hours with the 

valve closed.

Operating and fault messages

All data registered by the actuator can be queried 

via Modbus. The state of the hydraulics can be 

assessed on the basis of these data and possible 
errors and failures can be detected at an early stage.

Bus monitoring

The bus failure detection can be parametrized via 
Modbus (see section 

6.2 on page 12

).

Summary of Contents for Aktor M ST L Modbus

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L Modbus 24 V DN 40 50...

Page 2: ......

Page 3: ...3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Basic functions 7 3 2 2 Calculation functions 8 3 2 3 Limitation function...

Page 4: ...1 2019 6 3 2 Via the Modbus parametrization 13 6 4 Manual operation 13 6 4 1 Extending the drive stem 13 6 4 2 Retracting the drive stem 14 7 Maintenance 14 8 Removal 14 9 Disposal 14 10 Appendix 15 1...

Page 5: ...le connec tions 1 3 Extent of supply Electromotive actuator Aktor M ST L Modbus 24 V Operating instructions 1 4 Contact Address OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY Technic...

Page 6: ...s injury if not avoided CAUTION Indicates a possible danger with lower risk The situation may lead to minor and revers ible injury if not avoided NOTICE Indicates a situation that may lead to damage t...

Page 7: ...e actuator is operated with steady control The control signal 0 100 is transmitted via Modbus communication The current position 0 100 can be queried via Modbus Valve anti blocking function The actuat...

Page 8: ...d via Modbus and the calculated current output When exceeded the volume flow will be reduced until the limit value is reached again 3 2 4 Control function Output control registers 130 200 301 310 311...

Page 9: ...s Permissible fluid temperature in the valve 0 120 C Ambient tempera ture 0 50 C Ambient humidity In operation 0 85 r h not condensing Out of operation 0 85 r h not condensing Overvoltage cate gory De...

Page 10: ...ches Bit 1 bis 6 are set to OFF see section 5 3 1 on page 12 5 1 Fitting of the actuator Make sure that there is enough space for the installation of the actuator The actuator must only be connected t...

Page 11: ...e to dripping water f Do not feed the cable in from the top 1 Remove the casing cover 2 Connect the data lines for the Modbus and if required the lines for the universal inputs according to the assign...

Page 12: ...D is located under the casing cover above the terminal on the right hand side and dis plays the operating status of the actuator The status LED is visible even when the cover is closed Status LED Mean...

Page 13: ...error message will be gen erated again immediately 5 Baud rate change The currently set parameters of the register addresses 105 107 are applied 6 4 Manual operation The manual mode is only intended...

Page 14: ...Disconnect all electrical connections 4 Press the push button to release the latched valve stem position 1 in Illust 2 on page 7 5 Unscrew the collar nut 6 Remove the actuator from the valve Also remo...

Page 15: ...1 23 2 uint16 HW identifier r e g 0x00F1 3 uint16 SerNum1 r 0 65535 4 uint16 SerNum2 r 0 65535 5 uint16 SerNum3 r 0 65535 101 uint16 Time hour r w 0 23 to be set manually no battery buffered RTC 102...

Page 16: ...input 3 KP10 4 NI1000_DIN 5 NI1000_LG 6 PT1000 8 Y output 0 10V register 426 9 Y feedback 0 10V register 401 10 Change over output 0V cooling 5V shut off 10V heating 127 uint16 Inversion P2 input r w...

Page 17: ...ure control according to register differential temperature 201 uint16 Change over mode r w 0 Shut off 1 Heating 2 Cooling 3 Automatic according to flow temperature 300 uint16 Nominal value room temper...

Page 18: ...w Current flow temperature in C 10 write protected in case of assigned source P1 or P2 405 int16 Return temperature r w Current return temperature in C 10 write protected in case of assigned source P...

Page 19: ......

Page 20: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101274584 V01 11 2019...

Reviews: