Appendix 

„Aktor M ST L Modbus“

18

101274584-V01.11.2019

318

uint16

Operating status  / 

Error

r

0x0000: Normal operation, no message

0x0001: Disturbance internal  memory 

0x0002: Disturbance internal AD conversion 

0x0004: Disturbance valve adaptation 

0x0008: Disturbance internal motor function 

0x0010:  P1 range excess

0x0020: P2 range excess

0x0040: Disturbance calculation/control functions

0x0080: Permanent blocking of the valve

0x0100: Command execution test run/adaptation active

319

uint16

Current flushing timer

r

Minutes remaining until flushing

320

uint16

Current valve an-
ti-blocking timer

r

Minutes remaining until valve anti-blocking

321

uint32

Operating time

r

Seconds

323

uint32

Travel counter

r

mm

400

uint16

Nominal value volume 

flow (control signal)

r/w

0..10000 = 0..100%

401

uint16

Actual value volume 

flow

r

0..10000 = 0..100%

402

uint16

Current calculated 

volume flow

r

l/h

403

int16

Room temperature

r(w)

°C*10  (write protected in case of assigned source P1 or P2)

404

int16

Flow temperature

r/(w)

Current flow temperature in °C*10 (write protected in case 
of assigned source P1 or P2)

405

int16

Return temperature

r/(w)

Current return temperature in °C*10 (write protected in case 
of assigned source P1 or P2)

406

int16

Differential temperature r

Calculated difference from flow/return temperature register 
in K*10

407

uint16

Leakage warning

r

0: No warning; 1: Leakage detected (valve closed for more 
than 6h, differential temperature exceeding 8 K)

408

uint16

Digital contact 1

r

0/1

409

uint16

Digital contact 2

r

0/1

410

uint16

Current calculated 
thermal output

r

kW*10 (display in cooling and heating mode without signs.)

411

uint16

Energy since 0 a.m.

r

kWh*10

412

uint16

Energy last 24h

r

kWh*10

413

uint16

Change-over status

r

0: Shut-off ; 1: Heating ; 2: Cooling

414

uint16

Current maximum vol-

ume flow

r

Current value in l/h

415

uint16

Initial value PI controller

r

0..100%

418

uint16

Nominal position

r

mm*10

419

uint16

Actual position

r

mm*10

420

uint16

Learned total travel

r

mm*10

424

int16

Sensor input P1

r

V*100,°C*10; 0/1

425

int16

Sensor input P2

r

V*100,°C*10; 0/1

426

uint16

Y output P2

r/w

Voltage value 0..1000 for output signal 0..10V (for configura

-

tion I/O type P2: 8: Y output 0..10V)

Summary of Contents for Aktor M ST L Modbus

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L Modbus 24 V DN 40 50...

Page 2: ......

Page 3: ...3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Basic functions 7 3 2 2 Calculation functions 8 3 2 3 Limitation function...

Page 4: ...1 2019 6 3 2 Via the Modbus parametrization 13 6 4 Manual operation 13 6 4 1 Extending the drive stem 13 6 4 2 Retracting the drive stem 14 7 Maintenance 14 8 Removal 14 9 Disposal 14 10 Appendix 15 1...

Page 5: ...le connec tions 1 3 Extent of supply Electromotive actuator Aktor M ST L Modbus 24 V Operating instructions 1 4 Contact Address OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY Technic...

Page 6: ...s injury if not avoided CAUTION Indicates a possible danger with lower risk The situation may lead to minor and revers ible injury if not avoided NOTICE Indicates a situation that may lead to damage t...

Page 7: ...e actuator is operated with steady control The control signal 0 100 is transmitted via Modbus communication The current position 0 100 can be queried via Modbus Valve anti blocking function The actuat...

Page 8: ...d via Modbus and the calculated current output When exceeded the volume flow will be reduced until the limit value is reached again 3 2 4 Control function Output control registers 130 200 301 310 311...

Page 9: ...s Permissible fluid temperature in the valve 0 120 C Ambient tempera ture 0 50 C Ambient humidity In operation 0 85 r h not condensing Out of operation 0 85 r h not condensing Overvoltage cate gory De...

Page 10: ...ches Bit 1 bis 6 are set to OFF see section 5 3 1 on page 12 5 1 Fitting of the actuator Make sure that there is enough space for the installation of the actuator The actuator must only be connected t...

Page 11: ...e to dripping water f Do not feed the cable in from the top 1 Remove the casing cover 2 Connect the data lines for the Modbus and if required the lines for the universal inputs according to the assign...

Page 12: ...D is located under the casing cover above the terminal on the right hand side and dis plays the operating status of the actuator The status LED is visible even when the cover is closed Status LED Mean...

Page 13: ...error message will be gen erated again immediately 5 Baud rate change The currently set parameters of the register addresses 105 107 are applied 6 4 Manual operation The manual mode is only intended...

Page 14: ...Disconnect all electrical connections 4 Press the push button to release the latched valve stem position 1 in Illust 2 on page 7 5 Unscrew the collar nut 6 Remove the actuator from the valve Also remo...

Page 15: ...1 23 2 uint16 HW identifier r e g 0x00F1 3 uint16 SerNum1 r 0 65535 4 uint16 SerNum2 r 0 65535 5 uint16 SerNum3 r 0 65535 101 uint16 Time hour r w 0 23 to be set manually no battery buffered RTC 102...

Page 16: ...input 3 KP10 4 NI1000_DIN 5 NI1000_LG 6 PT1000 8 Y output 0 10V register 426 9 Y feedback 0 10V register 401 10 Change over output 0V cooling 5V shut off 10V heating 127 uint16 Inversion P2 input r w...

Page 17: ...ure control according to register differential temperature 201 uint16 Change over mode r w 0 Shut off 1 Heating 2 Cooling 3 Automatic according to flow temperature 300 uint16 Nominal value room temper...

Page 18: ...w Current flow temperature in C 10 write protected in case of assigned source P1 or P2 405 int16 Return temperature r w Current return temperature in C 10 write protected in case of assigned source P...

Page 19: ......

Page 20: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101274584 V01 11 2019...

Reviews: