background image

„Aktor M ST L Modbus“ 

Technical description

7

101274584-V01.11.2019

3.  Technical description

3.1  Construction

96

71

62

95

M30x1,5 DIN 13  

Illust. 1:  Side view

56

1

Illust. 2:  Front view

(1)

Push button for releasing the latched valve 

stem

3.2  Functional description

The full range of functions will only be available 
after parametrization of the Modbus.

Mini actuator Modbus for steady control in heating, 

ventilation and air conditioning systems.

Control is carried out via Modbus RTU communica

-

tion (RTU: Remote Terminal Unit).
Apart from the communication on the Modbus, two 
universal inputs (binary and analogue) are available. 

One of the inputs can be used as analogue output. 
The inputs are suitable for internal functions and for 
further processing of data in an automation station 

(Modbus master).

3.2.1  Basic functions

Automatic recognition of neutral point

The neutral point is detected during the initialisation 

run. A cyclical reinitialization is performed during 

operation.

Positioning

The actuator is operated with steady control. The 
control signal (0..100%) is transmitted via Modbus 

communication.

The current position (0..100%) can be queried via 
Modbus.

Valve anti-blocking function

The actuator features a valve anti-blocking function 

which can be activated. The cycle time can be con

-

figured via the Modbus parametrization.
If the value is zero, this function is deactivated.
The valve anti-blocking function will prevent sticking 

of the stem if the valve is not activated over a longer 
period.

Setting of valve characteristic lines

Different valve types with their characteristic lines 
can be selected via the Modbus parametrization. A 
minimum and a maximum volume flow are defined 

on the basis of these characteristic lines.

Configuration of the hydronic balancing values

A maximum volume flow (hydronic balancing) for the 
heating and cooling mode can be defined via the 
Modbus parametrization.

Temperature detection

The temperatures of the supply and return pipe can 

be detected via two connected temperature sensors 
and can be queried via Modbus.

Flushing function

The actuator features an automatic flushing function. 
During flushing, the valve is be temporarily fully open. 

Summary of Contents for Aktor M ST L Modbus

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L Modbus 24 V DN 40 50...

Page 2: ......

Page 3: ...3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Basic functions 7 3 2 2 Calculation functions 8 3 2 3 Limitation function...

Page 4: ...1 2019 6 3 2 Via the Modbus parametrization 13 6 4 Manual operation 13 6 4 1 Extending the drive stem 13 6 4 2 Retracting the drive stem 14 7 Maintenance 14 8 Removal 14 9 Disposal 14 10 Appendix 15 1...

Page 5: ...le connec tions 1 3 Extent of supply Electromotive actuator Aktor M ST L Modbus 24 V Operating instructions 1 4 Contact Address OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY Technic...

Page 6: ...s injury if not avoided CAUTION Indicates a possible danger with lower risk The situation may lead to minor and revers ible injury if not avoided NOTICE Indicates a situation that may lead to damage t...

Page 7: ...e actuator is operated with steady control The control signal 0 100 is transmitted via Modbus communication The current position 0 100 can be queried via Modbus Valve anti blocking function The actuat...

Page 8: ...d via Modbus and the calculated current output When exceeded the volume flow will be reduced until the limit value is reached again 3 2 4 Control function Output control registers 130 200 301 310 311...

Page 9: ...s Permissible fluid temperature in the valve 0 120 C Ambient tempera ture 0 50 C Ambient humidity In operation 0 85 r h not condensing Out of operation 0 85 r h not condensing Overvoltage cate gory De...

Page 10: ...ches Bit 1 bis 6 are set to OFF see section 5 3 1 on page 12 5 1 Fitting of the actuator Make sure that there is enough space for the installation of the actuator The actuator must only be connected t...

Page 11: ...e to dripping water f Do not feed the cable in from the top 1 Remove the casing cover 2 Connect the data lines for the Modbus and if required the lines for the universal inputs according to the assign...

Page 12: ...D is located under the casing cover above the terminal on the right hand side and dis plays the operating status of the actuator The status LED is visible even when the cover is closed Status LED Mean...

Page 13: ...error message will be gen erated again immediately 5 Baud rate change The currently set parameters of the register addresses 105 107 are applied 6 4 Manual operation The manual mode is only intended...

Page 14: ...Disconnect all electrical connections 4 Press the push button to release the latched valve stem position 1 in Illust 2 on page 7 5 Unscrew the collar nut 6 Remove the actuator from the valve Also remo...

Page 15: ...1 23 2 uint16 HW identifier r e g 0x00F1 3 uint16 SerNum1 r 0 65535 4 uint16 SerNum2 r 0 65535 5 uint16 SerNum3 r 0 65535 101 uint16 Time hour r w 0 23 to be set manually no battery buffered RTC 102...

Page 16: ...input 3 KP10 4 NI1000_DIN 5 NI1000_LG 6 PT1000 8 Y output 0 10V register 426 9 Y feedback 0 10V register 401 10 Change over output 0V cooling 5V shut off 10V heating 127 uint16 Inversion P2 input r w...

Page 17: ...ure control according to register differential temperature 201 uint16 Change over mode r w 0 Shut off 1 Heating 2 Cooling 3 Automatic according to flow temperature 300 uint16 Nominal value room temper...

Page 18: ...w Current flow temperature in C 10 write protected in case of assigned source P1 or P2 405 int16 Return temperature r w Current return temperature in C 10 write protected in case of assigned source P...

Page 19: ......

Page 20: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101274584 V01 11 2019...

Reviews: