E-216-5N-E
23
(8) Batch cancellation
If you want to cancel the batch operation in mid-flow, stop the operation temporarily, and then press "STOP" +
"RESET". At this time, the total display part will be reset to 0. If you press STOP + RESET while the pump is operated,
the operation will be stopped regardless of delay timer count value.
(9) Reset start function
Normally, the batch does not start without reset after the completion of batch, however, if the reset start function is
enabled by setting parameter, the batch start will be enabled without reset after the completion of batch. However,
while an alarm is generated, the batch does not start without resetting the alarm.
(10) Interlock function
If the external interlock signal is turned OFF, the operation cannot be started.
If the interlock signal is turned OFF during the batch operation, an alarm will be generated and the batch will be
temporarily stopped.
If the interlock signal is not used, short-circuit it with terminal block.
(11) Scaler function
If a pulse signal to be input is an unscaled pulse, the batch operation will be implemented by multiplying the
constant inherent to the flowmeter and converting it to integer industrial unit quantity.
(12) Accumulated counter value setting function
The accumulated counter value can be set to an arbitrary value within the range 0 to 999999 (can be set by
editing parameter).
If it is set to 0, it can be handled as zero reset. The value can be counted up to 999999999 (9 digits) on the
display.