28
3.3.7.5 Altitude adjustment
All valves have been preset and certified for installation at elevations from 0 - 4500 feet (0-1372m)
above sea level. When installing this insert at higher elevations, it is necessary to decrease the input
rating, by changing the existing burner orifice to a smaller size, consult local codes. Input should be
reduced 4% for each additional 1000 feet above sea level. Use Tables 5A & 5B or check with the
local gas authorities for proper orifice size identification. For the USA, derate the heater from sea
level according to the gas installation code.
Altitude adjustment by changing the burner orifice
(Natural Gas)
ALTITUDE
up to (ft)
REDUCTION
(%)
ORIFICE SIZE
(DMS)
TARGET
INPUT
(BTU/hr)
MANIFOLD
PRESSURE
(in.wc)
4500
-
36
35,000
3.5
5500
4
37
33,600
3.5
6500
8
38
32,200
3.5
7500
12
39
30,800
3.5
8500
16
40
29,400
3.5
9500
20
40
28,000
3.5
10500
24
41
26,600
3.5
11500
28
42
25,200
3.5
TABLE 5A
(Propane / LP Gas)
ALTITUDE
up to (ft)
REDUCTION
(%)
ORIFICE SIZE
(DMS)
TARGET
UNPUT
(BTU/hr)
MANIFOLD
PRESSURE
(in. wc)
4500
-
50
35,000
10
5500
4
51
33,600
10
6500
8
51
32,200
10
7500
12
52
30,800
10
8500
16
52
29,400
10
9500
20
53
28,000
10
10500
24
53
26,600
10
11500
28
54
25,200
10
TABLE 5B