Door open for heating up:

• 

The stove door is opened for heating up

• 

The heating up phase begins with the closing of 

the door
• 

The combustion air register opens

Line 2 on the display (= continuous text)

: Status: 

Door open – register open – (TEMP2 = 27 °C)

Heating up state:

• 

Is activated with the closure of the door

• 

The combustion air register is open

• 

The temperature in the combustion chamber is 

>50°C-<250°C 

Line 2 on the display (= continuous text):

Status: Anheizen – Tür geschlossen – Klappe offen – 
Heating time= 2min – (TEMP2= 27°C)

Heating state

• 

Wird ab einer Temperatur >250°C  aktiviert

• 

The combustion air register is open

• 

The maximum temperature is stored

• 

Determination of the optimal transition    

temperature to embers state

Line 2 on the display (= continuous text)

:

Status: Heating – door closed – register open –
heating time = 25 min – (TEMP2 = 230 °C)

Embers state:

• 

Is activated when the optimal transition  

 

        temperature is reached
• 

The combustion air register closes

• 

The display is dimmed

• 

The  heating  time  stops  and  the  embers  phase               

        begins
• 

Optimal heat storage is enabled

Line 2 on the display (= continuous text): 

Status: Embers – door closed – register closed –
heating time = 100 min – (TEMP2 = 230 °C)

Summary of Contents for ABS Combustion Control V2.2

Page 1: ...Operating Manual Operating Manual LED WLAN DISPLAY of the ORTNER Combustion Control V2 2 ORTNER control installed on Serial number ...

Page 2: ...ORTNER Inside ORTNER Speicherecke 09 70 40 38 Design black ...

Page 3: ...ations on the display of each heating phase 10 WLAN variant 12 Visualization of the combustion phases with LED 12 Visualization of the combustion phases via the WLAN module 12 Installation of the WLAN module with mobile devices 13 Integration in an existing personal network 14 Integration has failed Now what 16 Error messages and their correction 18 Heating up errors 18 Defective sensor 18 Tempera...

Page 4: ... ABS offers 3 different options ORTNER control with LED display ORTNER control with LED display and WLAN ORTNER control with display black or white The ORTNER combustion control Simple and elegant Fig 1 LED variant Fig 2 Display black Fig 3 WLAN view on smartphone 1 2 3 ...

Page 5: ...um efficiency By determining the maximum temperature in the heating phase and a calculation based thereon the optimum shutoff time of the combustion air flap is defined At this time the combustion air damper is automatically closed and the embers phase begins In this phase an open combustion air flap would lead to an undesirable faster cooling of the furnace installation Thanks to the control the ...

Page 6: ...fety In the event of a power failure the combustion air register of the control unit is opened automatically Initial start up During the initial start up and restart as well as following a power failure for safety reasons the control always starts in the heating up phase and the combustion air register remains open Therefore in the event of a power failure during the heating process the fuel is bu...

Page 7: ...Page 7 ORTNER Inside ORTNER Grundofen 11 42 59 Appearance Traditional tile green ...

Page 8: ...he temperature in the combustion chamber is 50 C The combustion air register is closed The door s are opened for heating up Door open The door is open for the insertion the fuel The combustion air register opens The masonry heater is in the heating up phase Heating up state Is activated with the closure of the door The combustion air register is open The temperature in the combustion chamber is 25...

Page 9: ... embers The masonry heater switches to the heating phase 600 C Heating state The temperature drops to 600 C The combustion air register is open The masonry heater switches to the embers or storage phase Embers state Is activated when the optimal transition temperature is reached The combustion air register closes The embers phase begins Optimal heat storage is enabled Renewed refuelling with wood ...

Page 10: ...data is presented on the display during the combustion In this manner you can continuously see the temperature and the status of the heating process When the control switches into the embers phase the display will dim Only when a new combustion is begun will the display light up again brightly and all status messages will be displayed Visualization of the combustion phases with glass display Curre...

Page 11: ...pe offen Heating time 2min TEMP2 27 C Heating state Wird ab einer Temperatur 250 C aktiviert The combustion air register is open The maximum temperature is stored Determination of the optimal transition temperature to embers state Line 2 on the display continuous text Status Heating door closed register open heating time 25 min TEMP2 230 C Embers state Is activated when the optimal transition temp...

Page 12: ...of the combustion on mobile devices Visualization of the combustion phases with LED Visualization of the combustion phases via the WLAN module Green Standby mode Blue Door open Orange Heating up Red Heating 600 C Purple Ember phase Light purple Heating 600 C Red Heating 600 C Status of the door Current temperature 1 Current combustion phase Heating time Status of the combustion air register Temper...

Page 13: ... lower 5 Launch your web browser Internet and enter http 1 2 3 4 in the search bar Congratulations you have successfully connected with the WLAN module and can now access all data online The ORTNER combustion control Using the WLAN module you can also receive all data on mobile devices The combination with the LED display also serves as an additional variant in order to be able to see the current ...

Page 14: ... power 2 Set the switch on the WLAN module to the centre position and connect the module to the control 3 Switch the control on 4 Move the switch on the WLAN module to the left after at least 5 seconds and return it to the centre position after approx 1 second 5 Using a device with wireless connectivity notebook smartphone tablet etc search for the ORTNER WLAN and connect to this 6 Open a web brow...

Page 15: ...eive a list with the available networks 8 Select the desired network and enter the password of your personal network in Pass phrase The settings are saved by pressing Save Configuration 9 Switch the control off and back on after approx 5 seconds ...

Page 16: ...ilities 1 Windows Use the SoftPerfect Network Scanner application http www softperfect com download freeware netscan zip 2 First press Auto Detect IP Range and then Start Scanning 3 Search the MAC address that is noted on the module s mounting e g 00 06 66 81 05 3F ...

Page 17: ...tely above it Enter this in your web browser If you have located the IP address of the module the page can be added as a quick access to the home or start screen Instructions for Android 1 Open the page using the IP address in the Chrome browser 2 Touch the three small dots in the upper right corner to open the menu 3 Select Add to Home Screen whereby the name can still be changed 4 The icon with ...

Page 18: ...ve 250 C within 60 min This means that the fire fails to start burning properly e g the wood is too damp An insufficient amount of wood was inserted or replenished Correction Following a power failure or after each opening and closing of the door the control switches into the heating up phase and the error message is acknowledged The combustion phases are run through again However when the tempera...

Page 19: ...lease contact your stove fitter in order to have the thermocouple replaced Temperature at rest LED lit and flashing Temperature at rest Display text of the glass display TEMP1 52 C Temperature increase Door closed Temperature increase Register open Temperature increase Temp2 38 C Possible cause Temperature increase in the combustion chamber 50 C by the self ignition of the inserted wood amount as ...

Page 20: ...pression fitting of the LED on the control is secured correctly the cable or the LED is defective Please inform your stove fitter in order to have the LED replaced Measures for improvement and avoidance should be taken in order to prevent the damage from occurring again Please consult us Door open although the door is closed LED lit continuously Door open Display text of the glass display TEMP1 45...

Page 21: ... closed although the door is open LED lit continuously Standby mode Display text of the glass display TEMP1 38 C Status Standby mode Possible causes Screwed connection loose on the control or Cable connected incorrectly Correction Check the contact point of the door for contamination or residue and if necessary remove this with fine sand paper Additionally check the position of the magnet at the d...

Page 22: ...Notes ...

Page 23: ...and misprints reserved No responsibility is accepted for the correctness of this information The simultaneous use of the male and female form is avoided in order to ensure increased readability All personal designations apply to both genders This manual and all articles and images contained in it are subject to copyright The reproduction even only in extracts as well as any form of usage without p...

Page 24: ...ORTNER GmbH Hürmer Straße 36 A 3382 Loosdorf Melk T 43 0 2754 2707 F 43 0 2754 2708 technik ortner cc at www ortner cc at ...

Reviews: