IG-123-EN version 11; 23/07/2021
46
Operations sequence
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Disconnection
Press the "0" pushbutton to disconnect the circuit-breaker.
Figure 7.20.
Circuit-breaker opened indicator
Figure 7.21.
Starting position of the
cpg
.0-v
disconnector
Insert the lever in the feeder disconnector's actuating shaft.
Then turn 90º anti-clockwise. Check that the disconnector
status indicator shows opened.
Figure 7.22.
Feeder disconnector opening sequence