IG-123-EN version 11; 23/07/2021
49
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Operations sequence
Disconnection
Figure 7.29.
Starting position of the
cpg
.0-v
disconnector
Press the "0" pushbutton to disconnect the circuit-breaker.
Figure 7.30.
Circuit-breaker opened indicator
Insert the lever in the feeder disconnector's actuating shaft.
Then turn 90º ANTI-CLOCKWISE. Check that the feeder
disconnector status indicator shows opened.
Figure 7.31.
Feeder disconnector opening sequence