IG-123-EN version 11; 23/07/2021
32
Installation
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Continuation
Cubicle
model
Manu-
facturer
Connector Connector
series
Nº
terminals
Terminal
configuration
Max. rated
current
connector
[A]
Total
connector
length
[mm]
Max. diameter
on insulation
admitted by
the connector
[mm]
cpg
.0-v/s
24-36 kV
31.5 kA
630-1250 A
cpg
.0-vl
24-36 kV
31.5 kA
630-1250 A
Nexans
EUROMOLD
Screened
400TB
1 cable
400TB + CUP
800
255
37.5
2 cables
400TB + M440CP
+ 400TB + CUP
800
500
37.5
3 cables
400TB +
400TB +
400TB + CUP
800
745
37.5
1 cable + SA
400TB + 400PB-10SA
+ CUP
800
410
37.5
2 SA
400TB +
400TB + 400PB-10SA +
CUP
800
655
37.5
440TB
1 cable
440TB + CUP
1250
255
56
2 cables
440TB + M440CP
+ 440TB + CUP
1250
500
56
3 cables
440TB +
440TB +
440TB + CUP
1250
745
56
1 cable + SA
440TB + 400PB-10SA
+ CUP
1250
410
56
2 SA
440TB +
440TB + 400PB-10SA +
CUP
1250
655
56
480TB
1 cable
480TB + CUP
1250
185
40.5
2 cables
480TB + 804PB + CUP
1250
295
40.5
3 cables
480TB + 804PB
+ 804PB + CUP
1250
405
40.5
4 cables
480TB + 804PB + 804PB
+ 804PB + CUP
1250
515
40.5
5 cables
480TB + 804PB + 804PB
+ 804PB + 804PB + CUP
1250
625
40.5
1 cable + SA
480TB + 800SA + CUP
1250
290
40.5
2 SA
480TB + 804PB
+ 800SA + CUP
1250
400
40.5
3 SA
480TB + 804PB + 804PB
+ 800SA + CUP
1250
510
40.5
4 SA
480TB + 804PB + 804PB
+ 804PB + 800SA + CUP
1250
620
40.5
484TB
1 cable
484TB + CUP
1250
185
56
2 cables
484TB + 804PB + CUP
1250
295
56
3 cables
484TB + 804PB + 804PB
+ CUP
1250
405
56
4 cables
484TB + 804PB + 804PB
+ 804PB + CUP
1250
515
56
5 cables
484TB + 804PB + 804PB
+ 804PB + 804PB + CUP
1250
625
56
1 cable + SA
484TB + 800SA + CUP
1250
290
56
2 SA
484TB + 804PB
+ 800SA + CUP
1250
400
56
3 SA
484TB + 804PB + 804PB
+ 800SA + CUP
1250
510
56
4 SA
484TB + 804PB + 804PB
+ 804PB + 800SA + CUP
1250
620
56
Continued on next page
Summary of Contents for velatia cpg.0
Page 79: ......