6. Menu
SETPOINTS
VFR Voltage Frequency Relay
6.14
Instruction Manual: VFR GBM 06/10/2021
Calibration Mode
Test HMI
Value
No
RANGE: Yes; No
Choose YES and press
ENTER
, to carry out a test of the display and the leds.
The display will show only dots and the leds will turn on for a couple of seconds.
Calibration Mode
Test BLE
Value
No
RANGE: Yes; No
Choose YES and press
ENTER
, to carry out a test.
Calibration Mode
Test Relays
Value
None
RANGE: NONE; AUX1; AUX2; AUX3; AUX4; AUX5; AUX6; AUX7; AUX8; ALL
Energize one or more output relays.
During the test, the chosen relay(s) will remain energized for five (5) seconds
and the navigation will be disabled throughout this time.
Calibration Mode
Device ID
Value
63aDedRt2f4=
A code like the example on the screen uniquely identifies the VFR.
It is useful in case the password gets lost or in case Orion Italia requires it for
technical support.
Calibration Mode
K TV
Value
1.000
RANGE: 0.800
1.200
Correction factor for TV ratio.
Second-level Password (PSW2) required.
Calibration Mode
K Time
Value
XXX
RANGE: -116
116
Internal clock calibration value.
DO NOT MODIFY.
This setpoint is factory calibrated.
If modified, contact Orion Italia.
Any modification applied to the following settings, can affect metering and protection functions.