6. Menu
SETPOINTS
VFR Voltage Frequency Relay
6.11
Instruction Manual: VFR GBM 06/10/2021
Output Relay
Aux7 Output Relay
Value
LATCHED
RANGE: LATCHED
-
LATCHED: once the associated protection has intervened, the Aux7 output
relay will function in Operating State.
When the fault condition ceases, it is necessary to manually RESET.
Output Relay
Aux8 Output Relay
Value
LATCHED
RANGE: LATCHED
-
LATCHED: once the associated protection has intervened, the Aux8 output
relay will function in Operating State.
When the fault condition ceases, it is necessary to manually RESET.
If Aux8 is used as Out of Service Relay, see [6.2
Setpoints: SYSTEM SETUP:
Out of Service Relay]
.
To connect the output contacts on the above section, use surge suppressors as specified on
Figure 2.4
and its
note
.
6.7 Setpoints: DIGITAL INPUT
Digital Input
Digital Input 1
Function
NONE
RANGE: NONE; Rem. Trip; Rem. Reset
Digital Input
D.I. 1 Remote Trip
Relays
Value
- - - - - - - -
RANGE: NONE; ANY COMBINATION OF AUX1, AUX2, AUX3, AUX4, AUX5,
AUX6, AUX7 OR AUX8
[6.7
Setpoints: DIGITAL INPUT
]
If Digital Input
=
Rem. Trip
Digital Input
Digital Input 2
Function
NONE
RANGE: NONE; Rem. Trip; Rem. Reset
Digital Input
D.I. 2 Remote Trip
Relays
Value
- - - - - - - -
RANGE: NONE; ANY COMBINATION OF AUX1, AUX2, AUX3, AUX4, AUX5,
AUX6, AUX7 OR AUX8
[6.7
Setpoints: DIGITAL INPUT
]
If Digital Input
=
Rem. Trip
6.8 Setpoints: EVENT RECORDER
You can enable/disable the recording of each type of event. All events, up to 100 maximum, will be stored in a memory buffer
operating in FIFO (First-In, First-Out) mode. Once 100 events are stored, the new event will push out the oldest one from the
Event List.
Event Recorder
System Events
Value
ENABLED
RANGE:
ENABLED; DISABLED