6. Menu
SETPOINTS
VFR Voltage Frequency Relay
6.12
Instruction Manual: VFR GBM 06/10/2021
Event Recorder
Digit Input
Events
Value
DISABLED
RANGE:
ENABLED; DISABLED
Event Recorder
Output Relays
Events
Value
DISABLED
(*)
RANGE:
ENABLED; DISABLED
Event Recorder
Voltage Protect.
Events
Value
ENABLED
RANGE:
ENABLED; DISABLED
Event Recorder
Frequency Protect.
Events
Value
ENABLED
RANGE:
ENABLED; DISABLED
6.9 Setpoints: MODBUS COMMUNICATION
This section contains the settings that allow the VFR communication with other devices.
Modbus Comm.
Modbus
Address
Value
1
RANGE: 1
247
STEPS: 1
Modify the Modbus ID.
Modbus Comm.
RS-485
Baudrate
Value
9600
RANGE:
9600; 19200; 38400; 57600; 115200
Select the Baud rate.
Modbus Comm.
RS-485
Config.
Value
8N1
RANGE:
8N1; 8N2; 8E1; 8E2; 8O1; 8O2
Specify the parity and the Stop-bit.
For further information, download
Modbus Memory Map
from the Orion Italia website.