PT-Link II N2-3 Interface
PT-Link II N2-3
®
Technical Guide
41
Appendix E - VCM N2 Parameters
VCM PT-Link II N2
®
Property Identifi er:
The PT-Link II N2
®
Link amends the following property identity to the
N2
®
property identifi er.
N2PropertyIdentifi er :
WattN2ScheduleForce
::= ENUMERATED {
NormalOperation
(0),
ForceOccupied
(1),
ForceUnoccupied
(2)
}
VcmUnitMode
::= ENUMERATED {
Unoccupied
(0),
RemoteContactOccupied (1),
NormalScheduleOccupied
(2),
PushButtonOrZoneOverride
(3),
HolidayModeActive
(4),
UnoccupiedZoneDemand
(5),
RemoteScheduleOverride (6),
CurrentOutputForceMode
(7),
SATHighOrLowCutOff
(8),
CO2OverrideInProgress
(9),
PurgeModeActive
(10)
}
VcmControlStatusBits
::= BIT STRING {
AhuControlEconomizer
(0),
NoOutdoorAirTempSensor
(1),
CarbonDioxideSensorPresent
(2),
HeatCoolStagingDisabled
(3),
Dehumidifi
cationMode
(4),
ModGasIIConnected
(5),
ReheatIIConnected
(6)
}
N2 Parameters for the VCM Controller
Parameter
Name
Object
Description
Limits
Expansion
Relay 4
ExRly4
BI: 136
Current status of
relay 9.
Expansion
Relay 5
ExRly5
BI: 137
Current status of
relay 10.
Expansion
Relay 6
ExRly6
BI: 138
Current status of
relay 11.
Expansion
Relay 7
ExRly7
BI: 139
Current status of
relay 12.
Expansion
Relay 8
ExRly8
BI: 140
Current status of
relay 13.
Expansion
Relay 9
ExRly9
BI: 141
Current status of
relay 14.
Expansion
Relay 10
ExRly10
BI: 142
Current status of
relay 15.
Expansion
Relay 11
ExRly11
BI: 143
Current status of
relay 16.
Expansion
Relay 12
ExRly12
BI: 144
Current status of
relay 17.
Expansion
Relay 13
ExRly13
BI: 145
Current status of
relay 18.
Expansion
Relay 14
ExRly14
BI: 146
Current status of
relay 19.
Expansion
Relay 15
ExRly15
BI: 147
Current status of
relay 20.
Expansion
Relay 16
ExRly16
BI: 148
Current status of
relay 21.