PT-Link II N2-3
®
Technical Guide
PT-Link II N2-3 Interface
34
Appendix D - SA Controller N2 Parameters
N2 Properties for SA Controller
Parameter
Name
Object
Description
Limits
Entering Air
Dewpoint
EaDpt
AI: 241
Current Entering Air
Dewpoint
Water Side
Economizer
Bypass
WSEByp
AI: 242
Current Water Side
Economizer Bypass
Position for 1st unit.
Water Side
Economizer
Bypass 2
WSEByp2
AI: 243
Current Water Side
Economizer Bypass
Position for 2nd unit.
Condenser
Position 1
CdPos1
AI: 246
Current Condenser
Position for 1st unit.
Condenser
Position 2
CdPos2
AI: 247
Current Condenser
Position for 2nd unit.
Dewpoint
Setpoint
DptSt
AO: 13
If the outdoor
dewpoint rises above
this setpoint, the
unit will activate the
Dehumidifi cation
Demand.
35
80
Occupied
Mode
Enable
Cooling
Setpoint
OcpClSt
AO: 42
If the control
temperature rises one
degree above this
setpoint, the control
will activate the cool-
ing demand. If the
control temperature
is the Supply Air Sen-
sor, then the cooling
demand is always
active.
0
99
Occupied
Mode
Enable
Heating
Setpoint
OcpHtSt
AO: 43
If the control
temperature drops
one degree below
this setpoint,
the control will
activate the heating
demand. If the
control temperature
is the Supply Air
Sensor, then there is
no heating demand.
99
Schedule
Force
SchdFrc
AO: 66
0 = Auto/
Unoccupied Mode
1 = Forced On
2 = Forced Off
0
2
Space
Sensor
Offset
SpcTpOst
AO: 71
If the Space
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100
100
SAT
Cooling
Setpoint
SaClSt
AO: 77
Supply Air Setpoint
in Cooling Mode.
40
80
SAT
Heating
Setpoint
SaHtSt
AO: 78
Supply Air Setpoint
in Heating Mode.
40
200
N2 Properties for SA Controller
Parameter
Name
Object
Description
Limits
Supply Air
Sensor Offset
SaTpOst
AO: 80
If the Supply Air
Temperature Sensor
is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100
100
Warm Up
Setpoint
WmupSt
AO: 91
In a VAV
application, upon
entering the
occupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
50
90
Coil
Temperature
Setpoint
CoilTpSt
AO: 107
This is the coil
suction temperature
target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately 10°F
above this setpoint.
35
70
Indoor
Humidity
Setpoint
InRhSt
AO: 120
If the indoor
humidity rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
0
100
Unoccupied
Cooling
Offset
UnClOst
AO: 124
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied Cool-
ing Setpoint out by
a user adjustable
amount. If you do
not want Cooling to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30